HVAC PT Charts

What Pressure Should R-454C Be?

Updated October 20, 2026

R-454C A2L Lower toxicity, lower flammability

You are on an R-454C system — a low-GWP A2L blend now going into new commercial refrigeration — with gauges connected and a big gap between the two saturation temperatures on the dial. That gap is the glide, and it is large.

Read superheat off the wrong curve on a blend that glides this much and you can be off by more than ten degrees — enough to flood or starve the evaporator while the gauge looks fine.

This page gives R-454C suction by application at the AHRI walk-in coil temperatures, head pressure by outdoor temperature, and the wide dew-to-bubble standing range.

R-454C suction is about 5.7–8.8 psig at a −20°F freezer coil and 40–46 psig at a 25°F cooler coil, with head around 239–311 psig at 95°F outdoors. It is a high-glide, low-GWP A2L blend, so read suction on the dew curve and treat standing pressure as a wide dew-to-bubble range.

R-454C pressures for walk-in coolers and freezers

Suction is set by the evaporator coil temperature. The AHRI 1250-2020 walk-in rating points — a 25°F cooler coil and a −20°F freezer coil — give the two suction bands you check most. Read suction on the dew curve.

Suction pressure by application (AHRI 1250-2020 walk-in coil temperatures)
ApplicationSuction (psig / kPa)
Walk-in cooler (25°F coil)40–46 psig 273–319 kPa
Walk-in freezer (−20°F coil)5.7–8.8 psig 39–61 kPa
Suction pressure by application (AHRI 1250-2020 walk-in coil temperatures) — AHRI 1250-2020, Tables 16 and 17

Head pressure by outdoor temperature

Head is set by the condenser and climbs with the outdoor air, the same on a cooler or a freezer. Find your outdoor temperature down the left column.

Head (discharge) pressure by outdoor temperature (65–115°F), at a condensing temperature 10–30°F above the outdoor air
OutdoorHead (psig / kPa)
65°F 18.3°C153–207 psig 1,055–1,429 kPa
70°F 21.1°C166–223 psig 1,142–1,534 kPa
75°F 23.9°C179–239 psig 1,232–1,645 kPa
80°F 26.7°C193–255 psig 1,328–1,761 kPa
85°F 29.4°C207–273 psig 1,429–1,883 kPa
90°F 32.2°C223–292 psig 1,534–2,010 kPa
95°F 35.0°C239–311 psig 1,645–2,143 kPa
100°F 37.8°C255–331 psig 1,761–2,282 kPa
105°F 40.6°C273–352 psig 1,883–2,427 kPa
110°F 43.3°C292–374 psig 2,010–2,578 kPa
115°F 46.1°C311–397 psig 2,143–2,736 kPa
Head (discharge) pressure by outdoor temperature (65–115°F), at a condensing temperature 10–30°F above the outdoor air — Computed from the CoolProp 7.2.0 pressure–temperature dataset.

Reading gauges on a high-glide blend

R-454C evaporates and condenses across a wide temperature range, so every pressure has a lower dew temperature and a much higher bubble temperature. Use the dew curve for suction and(/superheat-calculator/); use the bubble curve for the liquid line and(/subcooling-calculator/). Because the glide is large, an A2L-rated manifold that shows both scales — or a calculator that does the lookup — saves you from reading the glide as superheat.

Standing pressure: a wide dew-to-bubble range

Once the system has been off long enough for the pressures to equalize, R-454C reads across a wide dew-to-bubble band at the temperature of the coolest part of the system (indoor or outdoor) — for example 108–137 psig at 68°F (20°C). Treat standing pressure as a range, not a single number; the spread is the glide.

Standing pressure with the system off and equalized
Off temperatureStanding (dew–bubble, psig / kPa)
65°F 18.3°C102–130 psig 706–896 kPa
70°F 21.1°C112–141 psig 773–973 kPa
75°F 23.9°C123–153 psig 845–1,055 kPa
80°F 26.7°C134–166 psig 922–1,142 kPa
85°F 29.4°C145–179 psig 1,003–1,232 kPa
90°F 32.2°C158–193 psig 1,089–1,328 kPa
95°F 35.0°C171–207 psig 1,180–1,429 kPa
100°F 37.8°C185–223 psig 1,277–1,534 kPa
105°F 40.6°C200–239 psig 1,378–1,645 kPa
110°F 43.3°C216–255 psig 1,486–1,761 kPa
115°F 46.1°C232–273 psig 1,599–1,883 kPa
Standing pressure with the system off and equalized — Computed from the CoolProp 7.2.0 pressure–temperature dataset.

When R-454C readings are off

These are refrigeration faults; match a suspect reading to the pattern below, reading suction on the dew curve, then confirm with a calculator before adding refrigerant.

A healthy R-454C system at 95°F outdoors reads about 40–46 psig suction on a 25°F cooler coil, 5.7–8.8 psig on a −20°F freezer coil, and 239–311 psig head.

FaultSuctionHeadSuperheatSubcoolingFirst thing to check
Likely underchargelowlowhighlowFind and fix the leak, then recharge by weight
Likely overchargehighhighlowhighVerify condenser airflow, then recover to target
Likely restrictionlownormal–lowhighhighLook for a temperature drop across the filter-drier or liquid line, then check the metering device.
Likely metering device overfeedinghighlowlowlowA TXV or EEV stuck open or with a loose sensing bulb; on a fixed-orifice system, the piston size.
Suction, head, superheat and subcooling direction for each charge-and-system fault.

Confirm a reading before adjusting the charge: the pressure diagnostic tool, low suction pressure and high head pressure guides walk a reading to its cause.

Frequently asked questions

What pressures does R-454C run at in a walk-in freezer?

About 5.7–8.8 psig suction at the AHRI −20°F freezer coil temperature, read on the dew curve, with head near 239–311 psig at 95°F outdoors. Suction is set by the box, not the weather: it runs higher while a warm box pulls down and settles into this band once the box is at temperature. A reading well below it on a cold box points to an undercharge, a restriction, or a coil needing defrost.

What is R-454C standing pressure?

A range, not one number — once the pressures have equalized, R-454C reads across its dew-to-bubble band, about 108–137 psig at 68°F (20°C). The standing-pressure table above gives the band from 65 to 115°F. The wide spread is R-454C's glide.

What is R-454C saturation pressure at 20°C (68°F)?

About 108–137 psig at 68°F (20°C), given as a dew-to-bubble range because R-454C glides. The lower (dew) end is the saturated-vapor pressure; the higher (bubble) end is the saturated-liquid pressure. Use the dew end when comparing to a suction reading.

What is R-454C discharge pressure?

About 239–311 psig at 95°F outdoors, rising on hotter days because the condensing temperature sits above the outdoor air. Head is set by the condenser and ambient, not the box, so it is the same on a cooler or a freezer. Read the head chart above for your outdoor temperature.

How these numbers are calculated

Every pressure here is R-454C's saturation pressure at the stated temperature, calculated with CoolProp 7.2.0. Suction (low side) uses the saturated-vapor (dew) pressure; head (high side) uses the saturated-liquid (bubble) pressure.

Suction uses the AHRI 1250-2020 walk-in coil temperatures — 25°F for a cooler, −20°F for a freezer — read on the dew curve at the coil ±3°F; head is a condenser running 10–30°F above the outdoor air. We use 95°F as the reference because it is one of the AHRI 1250 outdoor rating temperatures for condensing units.

Sources: CoolProp 7.2.0; AHRI 1250-2020 (walk-in ratings). Your equipment maker's charging chart or the unit data plate overrides these reference values for that specific system.

Related