HVAC PT Charts

System Pressure Diagnostic Calculator

Enter your full set of pressure and temperature readings; the calculator computes SH, SC, condenser approach, and evaporator approach, then produces severity-ranked diagnostic flags with evidence and ordered recommendations.

Updated October 25, 2026

Operating conditions

Low side — suction

High side — liquid line

Enter all six measurements, then click Calculate.

Diagnostic flags surface patterns in the measurement combination. They are decision-support, not a substitute for hands-on equipment verification and the equipment OEM service literature. See high head pressure causes and superheat & subcooling fundamentals for the underlying diagnostic patterns and the procedures behind the recommendations.

Multi-input diagnostic — beyond pattern matching

Single measurements like superheat or subcooling answer specific questions about one side of the system. Two measurements together (the combined SH × SC matrix) form a 2D coordinate that classifies into eight patterns. A multi-input diagnostic adds two more dimensions — condenser approach and evaporator approach — for richer discrimination between root causes that the 2D matrix would lump together.

A condenser-fouling case and an overcharge case both show high SC, for instance, but condenser approach distinguishes them cleanly: fouling raises approach (condenser can't reject heat), overcharge doesn't (condenser still rejecting normally, just more liquid backed up). With both metrics in hand, the diagnostic shifts from "might be A or B" to "definitely A, with this evidence."

Four metrics, eight inputs, sixteen-plus distinct root causes
Adding ambient and return air temperatures unlocks approach calculations. The four derived metrics (SH, SC, cond approach, evap approach) span more diagnostic space than two metrics alone, distinguishing root causes that look identical in the SH × SC plane.

Approach temperatures — the missing diagnostic dimension

Approach temperature is the difference between the refrigerant's saturation temperature and the heat-transfer medium (air, water) on the other side of the coil. For an air-cooled condenser, approach = T_sat_discharge − T_ambient. For an evaporator, approach = T_return_air − T_sat_suction. The approach measures how efficiently the coil is moving heat.

Target approach by application
Application / coilNormal approachWhat high approach means
Air-cooled condenser, residential AC15-25°FDirty coil, blocked airflow, non-condensables, overcharge
Water-cooled condenser, chiller5-10°FTube fouling, low water flow
Air-cooled condenser, walk-in15-30°FDirty coil, condenser fan failure
Evaporator, residential AC20-40°FLow indoor airflow, dirty filter, blower problem
Evaporator, walk-in cooler10-20°FIced coil, low refrigerant, fan problem
Evaporator, chiller (flooded)2-5°FTube fouling, low water flow
Condenser approach severity (residential AC, °F above ambient)Low (look for undercharge)Normal — properly chargedElevated — fouling / overchargeALARM — approaching cutout0°F10°F20°F30°F40°F50°F60°FThese bands are this site's diagnostic heuristics from OEM service practice (Carrier, Trane), not a published standard

Condenser approach visualized for a residential AC: refrigerant saturates 15-25°F above ambient on a properly-running condenser. Approach climbing into the 25-40°F range indicates a condenser-side problem; above 40°F is approaching the high-pressure cutout. These bands are this site's diagnostic heuristics from OEM service practice (Carrier, Trane), not a published standard. (condensers), Carrier / Trane / Lennox service literature.

Severity classification — alarm / concern / caution / OK

The diagnostic ranks each flag by severity. Severity = magnitude of deviation × consequence of the underlying condition. This means a small SH deviation might warrant only a CAUTION while a large condenser approach deviation triggers ALARM, even if both deviations are technically "outside target."

Severity tiers
SeverityExamplesAction
ALARMZero / negative SH, negative SC, condenser approach > 40°F, discharge P near cutoutStop the system, investigate before restart.
CONCERNSH 20-30°F above target, SC < 3°F, condenser approach 25-40°FIdentify root cause, plan service action.
CAUTIONSH or SC 5-10°F off target, approach slightly elevated, pressure trends mismatchedVerify with additional measurement, schedule follow-up.
OKAll metrics in target rangeNo action; document baseline.

Real service problems — multi-flag diagnostic synthesis

Six scenarios where two or more flags fire at the same time. The multi-input diagnostic identifies the root cause that resolves all flags, distinguishing it from cases where multiple independent issues coexist.

1
Service problemR-410A (TXV)

Single-cause undercharge — three flags, one root cause

Scenario · R-410A TXV residential AC, 95°F outdoor, 75°F return air. Customer reports poor cooling. You take the full set of readings.

Measured at the manifold
Suction P
110 PSIG
Suction line
62°F
Discharge P
340 PSIG
Liquid line
98°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
110 PSIG 36.2°F sat evaporator saturation
340 PSIG 104.6°F sat condenser saturation
Derived
Superheat = 62.0 − 36.2 (dew) = 25.8°F above target 8-15°F
Subcooling = 104.6 (bubble) − 98.0 = 6.6°F below target 8-12°F
Condenser approach = 104.6 − 95.0 (ambient) = 9.6°F below target 15-25°F
Evaporator approach = 75.0 (return air) − 36.2 = 38.8°F in target 20-40°F
Investigate · Likely undercharge
High SH + low SC + low condenser approach all point to one cause: insufficient refrigerant. The low condenser approach is a direct consequence of the undercharge — less refrigerant means less condensing happening per pass, so the condenser doesn't need to climb above ambient to reject heat (because it's not rejecting much heat).
Fix
Find and repair the leak before recharging (leak-repair duties are size-based per 40 CFR 82.157 and 84.106; no blanket federal no-top-off rule), then evacuate and charge by weight. All three flags should clear once charge is correct.
2
Service problemR-410A (TXV)

Two independent causes — dirty filter + slight overcharge

Scenario · R-410A TXV system. Customer reports the AC cools but cycles on and off more than it should. Some readings look like overcharge, but evap approach is also low — hinting at two issues.

Measured at the manifold
Suction P
105 PSIG
Suction line
44°F
Discharge P
414 PSIG
Liquid line
101°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
105 PSIG 33.9°F sat evaporator saturation
414 PSIG 119.0°F sat condenser saturation
Derived
Superheat = 44.0 − 33.9 (dew) = 10.1°F in target 8-15°F
Subcooling = 119.0 (bubble) − 101.0 = 18.0°F above target 8-12°F
Condenser approach = 119.0 − 95.0 (ambient) = 24.0°F in target 15-25°F
Evaporator approach = 75.0 (return air) − 33.9 = 41.1°F above target 20-40°F
Investigate · Elevated subcooling — overcharge or condenser-side restriction
Two independent findings share this reading: a high evaporator approach (the coil can't pull the return air down to the refrigerant — low indoor airflow / dirty filter), and elevated subcooling (liquid backing up in the condenser — overcharge). Low indoor airflow LOWERS the suction saturation, which RAISES the evaporator approach; it does not lower it.
Fix
Restore indoor airflow first (filter, blower, coil), re-measure, and only then recover charge if subcooling stays high.
3
Service problemR-410A (TXV)

Condenser fouling — high SC but condenser approach is the smoking gun

Scenario · R-410A TXV system. SC is high (looks like overcharge) but the system has no recent service history. Could be overcharge — but the condenser-approach flag distinguishes overcharge from fouling cleanly.

Measured at the manifold
Suction P
130 PSIG
Suction line
60°F
Discharge P
445 PSIG
Liquid line
98°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
130 PSIG 45.0°F sat evaporator saturation
445 PSIG 124.5°F sat condenser saturation
Derived
Superheat = 60.0 − 45.0 (dew) = 15.0°F in target 8-15°F
Subcooling = 124.5 (bubble) − 98.0 = 26.5°F above target 8-12°F
Condenser approach = 124.5 − 95.0 (ambient) = 29.5°F above target 15-25°F
Evaporator approach = 75.0 (return air) − 45.0 = 30.0°F in target 20-40°F
Investigate · Elevated subcooling — overcharge or condenser-side restriction
Condenser fouling and overcharge BOTH raise the condenser approach and subcooling — this reading does not distinguish them on its own. Work the reversible cause first.
Fix
Clean the condenser coil and re-measure. Recover charge only if subcooling stays high after the coil is clean.
4
Service problemR-410A (TXV)

ALARM — zero superheat with elevated condenser approach

Scenario · R-410A TXV system. Compressor making loud knocking sounds. You connect gauges and find immediate red flags.

Measured at the manifold
Suction P
175 PSIG
Suction line
62°F
Discharge P
510 PSIG
Liquid line
96°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
175 PSIG 61.7°F sat evaporator saturation
510 PSIG 135.1°F sat condenser saturation
Derived
Superheat = 62.0 − 61.7 (dew) = 0.3°F below target 8-15°F
Subcooling = 135.1 (bubble) − 96.0 = 39.1°F above target 8-12°F
Condenser approach = 135.1 − 95.0 (ambient) = 40.1°F above target 15-25°F
Evaporator approach = 75.0 (return air) − 61.7 = 13.3°F below target 20-40°F
Action required · Very high condenser approach — heat rejection failure
Multiple severe alarms stack up: near-zero superheat (a saturated mixture at the compressor suction — slugging risk), extreme subcooling (liquid backed up in the condenser — severe overcharge), and a very high condenser approach (heat-rejection at its limit). Stop the system before restart.
Fix
Stop the system. Recover charge in measured steps, verify condenser airflow/cleanliness, and re-check superheat and subcooling before returning to service.
5
Service problemR-410A (fixed orifice)

Fixed-orifice system at 105°F outdoor — ACCA chart vs flags

Scenario · R-410A fixed-orifice (piston) residential AC, hot 105°F outdoor day, indoor 75°F / 65°F WB. You're charging by SH against the fixed-orifice charging-chart field target — but the diagnostic shows additional flags. How to interpret?

Measured at the manifold
Suction P
115 PSIG
Suction line
44°F
Discharge P
440 PSIG
Liquid line
108°F
Ambient
105°F
Return air
75°F
PT chart lookup (R-410A)
115 PSIG 38.5°F sat evaporator saturation
440 PSIG 123.6°F sat condenser saturation
Derived
Superheat = 44.0 − 38.5 (dew) = 5.5°F below target 8-25°F
Target superheat (65°F WB / 105°F DB) = 5°F fixed-orifice charging-chart target
Subcooling = 123.6 (bubble) − 108.0 = 15.6°F above target 8-14°F
Condenser approach = 123.6 − 105.0 (ambient) = 18.6°F in target 15-25°F
Evaporator approach = 75.0 (return air) − 38.5 = 36.5°F in target 20-40°F
OK · Superheat on target — properly charged
On a fixed-orifice system the charge is judged by superheat against the wet-bulb/dry-bulb target, not by subcooling. With superheat within tolerance of the target, the system is correctly charged for this hot-day condition.
Fix
Verify against the fixed-orifice charging-chart target printed on the unit; the chart on the equipment always takes precedence.
6
Service problemR-454C (LT walk-in freezer)

Commercial LT — diagnostic at the low end of operating envelope

Scenario · R-454C walk-in freezer LT (low-temp commercial), −20°F box target, 95°F ambient. You're checking diagnostic flags for a system the operator says is running but not maintaining box temp.

Measured at the manifold
Suction P
7 PSIG
Suction line
5°F
Discharge P
260 PSIG
Liquid line
108°F
Ambient
95°F
Box temp
−10°F
PT chart lookup (R-454C)
7 PSIG dew −20.4°F sat evap outlet — use for superheat
7 PSIG bubble −34.5°F sat evap inlet — reference only
260 PSIG bubble 111.3°F sat cond outlet — use for subcooling
260 PSIG dew 122.9°F sat cond inlet — reference only
Derived
Superheat = 5.0 − −20.4 (dew) = 25.4°F above target 10-20°F
Subcooling = 111.3 (bubble) − 108.0 = 3.3°F below target 5-15°F
Condenser approach = 111.3 − 95.0 (ambient) = 16.3°F in target 15-25°F
Evaporator approach = −10.0 (box) − −20.4 = 10.4°F in target 5-20°F
Investigate · Likely undercharge
At the discharge pressure the dew point is the WARMER curve and the bubble point the cooler one; subcooling is measured from the bubble point. Read the wide-glide blend on the correct curve before judging the charge.
Fix
Confirm curve selection, then verify charge by subcooling on the bubble curve at discharge pressure and superheat on the dew curve at suction pressure.

When to use this calculator vs the others

  • System Pressure Diagnostic (this page) — full multi-input synthesis with approach temperatures and severity-ranked flags. Use when you have all six readings (ambient, return air, suction P+T, liquid P+T) and want the deepest available diagnostic.
  • Combined PT/SH/SC — eight-pattern matrix view without approach temperatures. Use when you have the four pressure/temperature inputs but not ambient or return air.
  • Superheat Calculator — focused suction-side. Quick charging of fixed-orifice or TXV verification.
  • Subcooling Calculator — focused liquid-side. TXV / EEV charging primary metric.
  • High Head Pressure Causes — narrative decision tree for the condenser-side fault path. Use as a human-readable companion to the diagnostic flag output.

Primary sources behind the calculator and content

  • CoolProp 7.2.0 (Bell, Wronski, Quoilin, Lemort 2014, doi:10.1021/ie4033999) — REFPROP-compatible Helmholtz EOS for all saturation temperatures.
  • ASHRAE Handbook—Refrigeration (2022) — “Equipment and System Dehydrating, Charging, and Testing” (service and charging procedures).
  • ASHRAE Handbook—HVAC Systems and Equipment (2024) — “Condensers” (air- and water-cooled condenser approach temperatures), “Air-Cooling and Dehumidifying Coils” (evaporators), and “Liquid-Chilling Systems” (chiller approach targets).
  • EPA Section 608 — refrigerant handling certification, leak repair requirements.
  • OEM service literature — Carrier, Trane, Lennox, Daikin, Goodman, Mitsubishi service manuals; commercial refrigeration OEMs (Heatcraft, Hussmann, Bohn) for walk-in approach and SH / SC targets.

How to read your results

Superheat (°F)
Suction-line temperature minus the suction saturation (dew) temperature — how far the vapor has warmed past its boiling point. Compare to the per-system-type target shown (e.g. 8-15°F on TXV residential AC); high superheat points to undercharge, a metering restriction, or low load, while near-zero or negative superheat means liquid refrigerant is reaching the compressor (slugging risk).
Subcooling (°F)
Liquid saturation (bubble) temperature minus the measured liquid-line temperature — how far the liquid has cooled below its condensing point. Compare to the target shown (e.g. 8-12°F on TXV residential AC); high subcooling suggests overcharge or a condenser bottleneck, while low or negative subcooling suggests undercharge.
Suction saturation temperature (°F)
The saturation (dew) temperature the measured suction pressure converts to — the temperature at which refrigerant boils in the evaporator. It is the baseline the suction-line temperature is compared against to compute superheat, and it should sit below the indoor return-air temperature.
Discharge saturation temperature (°F)
The saturation (bubble) temperature the measured liquid/discharge pressure converts to — the temperature at which refrigerant condenses in the condenser. It is the baseline for both subcooling and condenser approach, and on a healthy system it sits above the outdoor ambient.
Condenser approach (°F)
Discharge saturation temperature minus outdoor ambient — how much hotter than the air the condenser must run to reject heat. Typically 15–25°F above outdoor air (high-efficiency units near the low end); a high approach indicates a dirty coil, blocked airflow, non-condensables, or overcharge, while a low or negative approach indicates undercharge (little liquid backed up in the coil).
Evaporator approach (°F)
Return-air temperature minus the suction saturation temperature — how much warmer the entering air is than the boiling refrigerant. Roughly 20-40°F on residential AC. HIGH (above range) points to low indoor airflow (dirty filter, failing blower) or evaporator starvation (undercharge, liquid-line restriction) — the coil can't pull the air down to the refrigerant. LOW (below range) points to high airflow, overcharge, high indoor load, or a compressor not pumping.
Diagnostic findings (severity-ranked flags)
Each finding carries a severity badge (ALARM, CONCERN, CAUTION, or OK), the evidence behind it, and ordered recommended actions. Read them top-down: an ALARM demands stopping the system before restart, a CONCERN identifies a likely root cause to service, a CAUTION warrants a confirming measurement, and OK means every metric is inside its target range.

How to use this calculator

  1. Pick the refrigerant in the system. Pick the system type (TXV, fixed-orifice, EXV, or MT / LT commercial) — target ranges adjust accordingly.
  2. Record outdoor ambient at the condenser inlet (not in direct sun) and indoor return-air at the air handler.
  3. Let the system run 10-20 minutes under load to stabilize. Connect manifold gauges to suction and discharge ports.
  4. Read suction pressure (low side) and discharge pressure (high side). Clamp temperature probes to suction line (within 6 inches of compressor) and liquid line (at condenser outlet). Insulate probes from ambient.
  5. Enter all six measurements and click Calculate. The diagnostic flags appear after you click Calculate — read them in priority order, alarms first.
  6. Follow the numbered recommendations for the highest-severity flag first.

Common errors

  • Measuring before stabilization — transient readings produce conflicting patterns. Wait 10-20 minutes under load.
  • Probing temperature without insulating from ambient.
  • Confusing high-side and low-side ports — reversed connections invert the diagnosis entirely.
  • Treating the highest-severity alarm as the only finding — multiple flags often share root causes; read the full list.
  • Using the diagnostic for transcritical CO₂ — saturation-based analysis doesn't apply above the critical point.
Underlying math

Formula

Superheat = T_suction_line − T_sat(P_suction, dew) Subcooling = T_sat(P_liquid, bubble) − T_liquid_line Condenser approach = T_sat(P_liquid, bubble) − T_ambient Evaporator approach = T_return_air − T_sat(P_suction, dew) Diagnostic flags fire when derived values fall outside per-system-type target ranges, with severity ranked by magnitude × consequence.

Source

Saturation values from CoolProp 7.2.0. Diagnostic patterns and recommended actions are hvacptcharts diagnostic heuristics from field service practice and equipment manufacturer service literature — not a published standard.

Worked example

R-410A TXV residential AC, 95°F outdoor, 75°F return air: Suction: 110 PSIG, 62°F Discharge: 340 PSIG, 98°F Derived: Suction sat (dew): 36.2°F → SH = 62 − 36.2 = 25.8°F (above 8-15°F target) Discharge sat (bubble): 104.6°F → SC = 104.6 − 98 = 6.6°F (below 8-12°F target) Condenser approach = 104.6 − 95 = 9.6°F (LOW — should be 15-25°F) Evap approach = 75 − 36.2 = 38.8°F (high end of normal) Flags (priority-sorted): CONCERN — Likely undercharge (high SH + low SC fingerprint, supported by low condenser approach) CAUTION — Verify with leak search before adjusting charge Recommendation order: 1. Leak search before adding refrigerant 2. Repair leak per EPA 608 3. Evacuate to 500 microns, charge by weight to nameplate

Related tools

Frequently asked

›What does this calculator do that the combined PT/SH/SC calculator doesn't?

The combined PT/SH/SC calculator computes superheat and subcooling and shows a 6-pattern interpretation. This diagnostic calculator extends the analysis with two more dimensions: condenser approach (discharge saturation vs ambient) and evaporator approach (return air vs suction saturation), then produces structured flags with severity, evidence, and ordered recommendations. The combined calculator answers 'is the charge correct?'; the diagnostic answers 'what's wrong and what should I do about it?'.

›What is condenser approach and why does it matter?

Condenser approach is the discharge saturation temperature minus the outdoor ambient. On a properly-running residential AC, the approach is typically 15-25°F (high-efficiency units near the low end) — the condenser needs that delta to reject heat to the air. An approach significantly above this range indicates the condenser can't reject heat as fast as the system is generating it: dirty coil, blocked airflow, non-condensables, or compressor inefficiency. Above ~40°F approach raises high-pressure-cutout risk and warrants stopping the system. These bands are hvacptcharts diagnostic heuristics drawn from OEM service practice, not a published standard; the equipment OEM service literature is the authoritative reference.

›What is evaporator approach and why does it matter?

Evaporator approach is the return-air temperature minus the suction saturation temperature. For residential AC the approach is typically 20-40°F depending on indoor humidity — the evap needs that delta to absorb heat from the air. A HIGH approach (above ~40°F) means the coil can't pull the air down toward the refrigerant: low indoor airflow (dirty filter, failed blower) or evaporator starvation (undercharge, TXV restriction, blocked liquid line). A LOW approach (below ~20°F) means the air is over the coil too briefly relative to the boiling refrigerant: high airflow, overcharge, high indoor load, or a compressor not pumping. The approach is independent of charge in a way that SH is not, so it gives an orthogonal diagnostic dimension.

›Why does the calculator ask for system type?

Target ranges for superheat and subcooling differ by metering device and application. TXV residential AC targets tight SH (8-15°F) with SC as the primary charge metric (8-12°F). Fixed-orifice residential AC uses a wider SH range read from the fixed-orifice charging chart — target superheat from the field approximation (3 × indoor WB − 80 − outdoor DB) / 2, indexed on indoor wet-bulb and outdoor dry-bulb. Walk-in cooler / freezer targets wider ranges (SH 8-20°F, SC 5-15°F). Without the system type the calculator uses a generic envelope; with it the flags are calibrated to what the specific equipment class expects.

›How accurate are the diagnostic patterns?

The patterns reflect well-established HVAC field-service conventions — high SH + low SC = undercharge is the textbook fingerprint, repeated across decades of service literature. The calculator surfaces these patterns reliably from the input combination, but doesn't account for every real-world variable (system age, recent service, equipment-specific quirks, ambient changes during the reading). Treat the flags as 'here's what to investigate' rather than 'definitive diagnosis'.

›What if multiple flags appear at the same time?

Read them in priority order — alarm before concern before caution before OK. An ALARM flag (negative SH, negative SC, very-high condenser approach) demands action before continuing operation. A CONCERN flag identifies a likely cause and recommends specific investigation. A CAUTION flag is a less-clear pattern that warrants verification. Multiple flags often share root causes (overcharge flag + high condenser approach can both result from the same overcharge condition).

›Can I use this on commercial refrigeration?

Yes — pick medium-temp or low-temp commercial system type. Target ranges adjust accordingly. Commercial systems have wider tolerance ranges on SH and SC than residential AC because case load, door openings, and defrost cycles introduce more variability into steady-state readings. For very-large industrial systems and transcritical CO₂, use the equipment OEM diagnostic procedures rather than these generic patterns.

›Does this work for R-744 (CO₂) transcritical systems?

Partially. The sub-critical low-side analysis works for CO₂ systems (R-744 saturation pressures below 87.8°F critical temperature are well-modeled). The transcritical high-side cannot be analyzed with the saturation-based logic — above the critical temperature there is no saturation pressure, so subcooling and condenser approach calculations don't apply. For CO₂ transcritical diagnostic work, refer to equipment OEM service literature; the patterns are different from sub-critical HVAC.

›Why does the calculator weight some patterns higher than others?

Severity is determined by both the magnitude of the deviation and the consequence. Zero superheat (slugging risk) is an ALARM because of immediate compressor-damage risk; high condenser approach during normal operation is a CONCERN because of long-term efficiency loss; slightly elevated subcooling alone is CAUTION because it might be early-stage and might be measurement error. The weighting follows established field-service severity-ranking conventions.

Data sources & provenance

Saturation temperatures come from CoolProp 7.2.0 (50 refrigerants), CoolProp 8.0.0 (5) and Chemours’ charts for R-514A (1).

This calculator is provided as a reference. Always verify pressure values against the equipment data plate and manufacturer service literature before charging or troubleshooting a specific system. Saturation pressure differs from operating pressure; see superheat & subcooling fundamentals.