Superheat Calculator
Enter the suction pressure and the suction-line temperature for any of 56 refrigerants to get superheat. For zeotropic blends the calculator uses the dew point, so high-glide refrigerants such as R-407C, R-454C and R-455A don't read 11.1–22.1°F high at a 40°F dew point.[2]
Updated November 10, 2026 · By Marko Visic, BSc Physics
Target superheat reference
Target superheat depends on the metering device. These ranges are general guidance; always defer to the equipment manufacturer's charging procedure[3].
| System type | Target superheat | Reference |
|---|---|---|
| Fixed orifice (residential AC) | 5–45°F, read from a chart of indoor wet-bulb and outdoor dry-bulb | California Title 24, Table RA3.2-2[1] |
| TXV (AC and heat pump) | 8–12°F typical; up to 15°F on high-TD coils | Sporlan Bulletins 10-9 and 10-11[3][4] |
| EXV | set by the equipment's controls | the manufacturer's figure |
| Refrigeration, medium temperature (40 to 0°F evaporator) | 6–8°F (Sporlan); 6–10°F at a 10°F design TD (Heatcraft) | [3][5] |
| Refrigeration, low temperature (0 to −40°F evaporator) | 4–6°F | [3] |
For fixed-orifice systems use the manufacturer's charging chart with outdoor dry-bulb and indoor wet-bulb temperatures rather than a single setpoint[1]. See Carrier R-410A charging chart for an example.
Chart range for R-410A: −40°F to 150°F.
What superheat is and why we measure it
Superheat is the temperature of refrigerant vapor above its saturation temperature at the same pressure. At any pressure, the saturation temperature is the boundary where liquid and vapor coexist; once the refrigerant has fully boiled, every degree above that saturation reading is one degree of superheat.
Superheat matters for two reasons. Liquid that reaches the compressor damages it: Copeland lists valve-plate, piston and connecting-rod damage from low superheat[8] and bearing wear from oil diluted by liquid floodback[9]. And on a fixed metering device, superheat is how Title 24 checks the charge: refrigerant is added when superheat is above the target and removed when it is below.[1]
Schematic of a residential split-system suction line, showing the temperature sensor clamped to the suction line near the outdoor unit's suction service valve in good contact with the line[1], and where the suction pressure is read. Source: California Title 24 Reference Appendix RA3.2[1].
Two metering devices, two different questions
What you do with a superheat reading depends entirely on whether the system uses a fixed-orifice metering device (piston, capillary tube, accurator) or a thermostatic expansion valve (TXV / EEV).
| Metering device | Charge by | Verify by | Typical SH |
|---|---|---|---|
| Fixed orifice (piston, captube) | Superheat (target from chart) | Match fixed-orifice chart target | 5–45°F (from the chart)[1] |
| TXV (thermostatic expansion valve) | Subcooling (charge to SC target) | Steady SH at TXV setpoint | 8–12°F typical, up to 15°F[3][4] |
| EEV (electronic expansion valve) | Subcooling | EEV control board diagnostic | set by its controls |
On a fixed metering device, Title 24 sets the charge by superheat: the target depends on the return-air wet bulb and the outdoor temperature, and refrigerant is added when superheat is above the target and removed when it is below.[1] A TXV modulates flow to hold a nearly constant superheat at the evaporator outlet[3].
On TXV / EEV systems, charge is set by subcooling instead[1]. Superheat on these systems shows whether the valve is working: Title 24 sets the charge by subcooling and uses superheat to check the metering device[1]. On a TXV system, confirm the charge by subcooling first; superheat outside the manufacturer's figure after that (Title 24's default window is 4–25°F) points to the metering device[1]. Sporlan's causes of high superheat on a TXV also include a refrigerant shortage, moisture and dirt[4].
Target superheat reference — fixed-orifice charging charts and OEM service literature
Title 24's Table RA3.2-2 gives the target from the return-air wet bulb and the outdoor air entering the condenser. A higher wet bulb raises the target and a warmer outdoor temperature lowers it.[1]
| Outdoor \ WB | 50°F | 52°F | 54°F | 56°F | 58°F | 60°F | 62°F | 64°F | 66°F | 68°F | 70°F | 72°F | 74°F | 76°F |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 55°F | 8.8 | 11.5 | 14.2 | 17.1 | 20.0 | 23.1 | 26.2 | 29.4 | 32.4 | 35.1 | 37.7 | 40.2 | 42.7 | 45.0 |
| 60°F | 7.0 | 9.8 | 12.6 | 15.4 | 18.2 | 21.0 | 23.8 | 26.6 | 29.6 | 32.4 | 35.1 | 37.8 | 40.4 | 42.9 |
| 65°F | — | 7.0 | 10.0 | 12.9 | 15.8 | 18.5 | 21.2 | 23.8 | 26.7 | 29.7 | 32.5 | 35.3 | 38.1 | 40.8 |
| 70°F | — | — | 6.4 | 9.7 | 12.7 | 15.7 | 18.4 | 20.9 | 23.9 | 27.0 | 30.0 | 33.0 | 35.9 | 38.7 |
| 75°F | — | — | — | 5.6 | 9.2 | 12.4 | 15.3 | 18.0 | 21.1 | 24.3 | 27.5 | 30.6 | 33.7 | 36.7 |
| 80°F | — | — | — | — | — | 8.7 | 12.0 | 15.0 | 18.3 | 21.7 | 25.0 | 28.3 | 31.6 | 34.8 |
| 85°F | — | — | — | — | — | — | 8.5 | 11.9 | 15.5 | 19.0 | 22.6 | 26.0 | 29.5 | 32.9 |
| 90°F | — | — | — | — | — | — | — | 8.8 | 12.8 | 16.5 | 20.1 | 23.8 | 27.5 | 31.1 |
| 95°F | — | — | — | — | — | — | — | 5.6 | 10.0 | 13.9 | 17.8 | 21.6 | 25.5 | 29.4 |
| 100°F | — | — | — | — | — | — | — | — | 7.3 | 11.4 | 15.4 | 19.5 | 23.6 | 27.7 |
| 105°F | — | — | — | — | — | — | — | — | — | 8.8 | 13.1 | 17.4 | 21.7 | 26.0 |
| 110°F | — | — | — | — | — | — | — | — | — | 6.4 | 10.8 | 15.3 | 19.9 | 24.4 |
| 115°F | — | — | — | — | — | — | — | — | — | — | 8.6 | 13.3 | 18.1 | 22.9 |
Heat pumps: American Standard's installation instructions approve checking the charge only in cooling mode[6].
Examples
Fixed orifice, R-410A. Return air at 67°F wet bulb and 95°F outdoors: Table RA3.2-2 gives a 12.0°F target.[1] The suction gauge reads 118.4 psig, a 40.0°F dew point for R-410A, and the suction line is 58.0°F, so superheat is 18.0°F: 6.0°F above the target and outside the installer's 5°F window. Title 24's procedure is to add refrigerant, run 15 minutes and measure again.[1]
TXV, R-410A. With the charge already set by subcooling, the suction gauge reads 130.1 psig, a 45.0°F dew point, and the suction line is 57.0°F: 12.0°F of superheat, inside Title 24's 4–25°F installer window.[1]
Blend, R-407C. The suction gauge reads 63.2 psig: a 40.0°F dew point and a 28.9°F bubble point at that pressure. With the suction line at 52.0°F, superheat is 12.0°F from the dew column; the bubble column would give 23.1°F, 11.1°F too high.[2]
Glide-aware curve selection — why dew is the right curve for superheat
Zeotropic blends boil across a temperature range at constant pressure. As liquid refrigerant enters the evaporator (bubble point) and progresses to fully vaporized (dew point), the saturation temperature rises by the glide value, even though the pressure is unchanged.
Suction-line superheat is measured downstream of the evaporator, where refrigerant is fully vaporized. The relevant saturation reference is the dew point: the temperature at which the last drop of liquid disappeared. Using the bubble point would treat the entry-side saturation as if it were the exit-side reference, overstating superheat by the glide value (bubble sits below dew, so subtracting it inflates the result).
Bubble and dew curves for R-407C from the site's PT data. The gap between them, the glide, narrows as pressure rises: 11.8°F at 25 psig and 8.7°F at 250 psig. Use the dew curve for superheat on the suction line and the bubble curve for subcooling on the liquid line.[2]
Glide at a 40°F dew point, from the site's PT data: R-454B 2.3°F, R-449A 9.5°F, R-407C 11.1°F, R-454C 14.0°F, R-455A 22.1°F. Reading the bubble column on R-455A would overstate superheat by that 22.1°F.
Six common superheat measurement mistakes
- Wrong curve on zeotropes. Using bubble pressure for saturation temperature on R-407C / R-454C / R-455A overstates superheat by the glide value (11.1–22.1°F at a 40°F dew point). This calculator uses the dew curve automatically — verify any paper PT chart you reference shows both columns and use the dew column for SH.
- Sensor in the wrong place. Title 24 clamps it to the suction line near the outdoor unit's suction service valve[1]; follow your equipment's literature where it says otherwise.
- Sensor loose on the line. Title 24 puts the suction-line sensor near the suction service valve, positioned to make good contact with the surface of the line.[1]
- Reading before steady state. Run the system at least 15 minutes before measuring[1]; American Standard asks for 20 minutes after start-up or any charge change[6]. Brief after-start spikes or transient values during defrost / cycle changes are not charging-decision data.
- Compressor inlet versus evaporator outlet. Superheat at the compressor inlet runs higher than at the evaporator: Sporlan's worked example reads 10°F at the valve's bulb and 30°F at the compressor inlet, at the same pressure.[7] Title 24 reads superheat on the suction line near the suction service valve.[1]
- PSIG vs PSIA mix-up. Service gauges read PSIG (gauge pressure above atmospheric); some refrigerant property software wants PSIA (absolute). PSIA = PSIG + 14.6959 at sea level. Mixing them up moves the R-410A saturation temperature by about 6.7°F at a 40°F coil.
When to use this calculator vs the others
- Superheat Calculator (this page) — suction-line measurement. Charge fixed-orifice systems; verify TXV operation; diagnose evaporator-side issues (undercharge, restriction, flooding).
- Subcooling Calculator: liquid-line measurement; Title 24 charges TXV and EXV systems by subcooling.[1]
- Combined SH / SC / PT — both sides plus pattern-matching diagnostic banner. Use for full system commissioning or comprehensive diagnostic.
- PT Calculator — raw saturation lookup, no measurement input. Reference tool for cross-checking or comparing refrigerants.
- System Pressure Diagnostic — high-low pressure × high-low SH / SC pattern matcher. Use when you have all four values and want a quick fingerprint identification (undercharge, overcharge, restriction, airflow problem, compressor issue).
Primary sources behind the calculator and content
Saturation temperatures come from CoolProp 7.2.0 (50 refrigerants), CoolProp 8.0.0 (5) and Chemours’ charts for R-514A (1).
- [1]California Energy Commission, Reference Appendices for the 2025 Building Energy Efficiency Standards (Reference Appendix RA3.2), CEC-400-2025-010-AP. July 2025 (in effect January 1, 2026). https://www.energy.ca.gov/sites/default/files/2025-07/CEC-400-2025-010-AP.pdf (accessed October 19, 2026)
- [2]Sporlan Form 5-492, System Considerations for Refrigerant Blends with Temperature Glide. Sporlan (Parker). 2017. https://www.parker.com/content/dam/Parker-com/Literature/Sporlan/Sporlan-pdf-files/Sporlan-pdf-Educational/Form-5-492-Refrig-Blends.pdf (accessed October 19, 2026)
- [3]Sporlan Bulletin 10-9, Thermostatic Expansion Valves: Theory of Operation, Application, and Selection. Sporlan (Parker). March 2011. https://www.parker.com/content/dam/Parker-com/Literature/Sporlan/Sporlan-pdf-files/Sporlan-pdf-010/10-9.pdf (accessed October 19, 2026)
- [4]Sporlan Bulletin 10-11, Thermostatic Expansion Valves: Installation, Field Service, and Assembly. Sporlan (Parker). June 2011. https://www.parker.com/content/dam/Parker-com/Literature/Sporlan/Sporlan-pdf-files/Sporlan-pdf-010/10-11.pdf (accessed October 19, 2026)
- [5]Heatcraft Unit Coolers Installation and Operations Manual, H-IM-UC. Heatcraft Refrigeration Products. June 2026. https://heatcraftrpd.com/dA/372b2b9e1e/H-IM-UC.pdf (accessed October 19, 2026)
- [6]American Standard, Installation Instructions: Split System Air Conditioner & Heat Pump, 1.5–5 Tons, R410A, 14 SEER (©2020), section 14.2. American Standard (Trane Technologies). 2020. https://www.tranetechnologies.com/content/dam/common/oxbox/heat-pumps/pre-doe_14_seer_(j4hp4)/InstallationManual_J4HP4_14SEER.pdf (accessed October 19, 2026)
- [7]Sporlan Form 10-135, Using P-T Analysis As A Service Tool. Sporlan (Parker). 2013. https://www.parker.com/content/dam/Parker-com/Literature/Sporlan/Sporlan-pdf-files/Sporlan-pdf-Miscellanous/Form-10-135_52013.pdf (accessed October 19, 2026)
- [8]Copeland Semi-Hermetic Compressors for A2L & A1 Applications, 2D*, 3D* & 8D*: Application Guidelines. Rev00, © 2024. https://media.copeland.com/312b0788-6715-4271-b1e3-b16b010ca95f/AGL_HA_ST_Discus_A2L_A1_EN_Rev00_FULL.pdf (accessed November 10, 2026). Section 7.3, Inadequate suction superheat, p. 32.
- [9]Copeland, Application Engineering Bulletin AE4-1400 R3: 1 to 5 Ton ZP*K6 R-410A Copeland™ Scroll Compressors. June 2024. https://webapps.copeland.com/online-product-information/Publication/LaunchPDF?Index=AEB&PDF=1400 (accessed November 10, 2026). p. 9, Accumulators.
- [10]Danfoss, Thermostatic Expansion Valve Troubleshooting, AC307572949567. 2017.12. https://assets.danfoss.com/documents/90976/AC307572949567en-010101.pdf (accessed October 19, 2026)
- [11]Sporlan Form 10-143, 12 Solutions for Fixing Common TEV Problems. Sporlan (Parker). 06/2012. https://www.parker.com/Literature/Sporlan/Sporlan%20pdf%20files/Sporlan%20pdf%20010/10-143.pdf (accessed October 19, 2026)
How to read your results
- Superheat (°F or °C)
- How many degrees the suction-line vapor sits above its saturation temperature; this is the vapor margin that keeps liquid out of the compressor. Compare it with your system's target: the chart value for a fixed orifice, or the manufacturer's figure for a TXV.
- Saturation temperature at suction pressure
- The temperature the entered suction pressure corresponds to on the PT chart; it is the baseline the superheat is measured from (superheat = line temp − this value). For zeotropic blends the tool reads the dew curve (labeled as such), which is the correct boundary for suction-line superheat; using the bubble curve would overstate superheat by the refrigerant's glide.
- Diagnostic banner
- A negative value means the line reads colder than the saturation temperature at that pressure, so the refrigerant there isn't superheated vapor. Check the probe position and contact, and the pressure reading. Any other value: compare with your target. Fixed orifice: Title 24's table or the manufacturer's chart, within 5°F. TXV or EXV, once the charge is set by subcooling: the manufacturer's range, or 4–25°F.[1]
How to use this calculator
- Pick the refrigerant in the system. Defaults to R-410A.
- Read the suction-line pressure from the low-side manifold gauge; most service gauges read PSIG by default.
- Clamp a temperature sensor to the suction line near the suction service valve, in good contact with the line, and read it after the system has run in cooling for at least 15 minutes.[1]
- Enter both values. The calculator returns superheat in °F (or °C if you toggle the unit) plus a diagnostic banner.
- Compare against your equipment's target superheat (OEM charging chart, TXV spec, or the fixed-orifice charging-chart reference below).
Common errors
- Reading the discharge pressure instead of the suction pressure. The suction is the LOW side; discharge is the HIGH side.
- On zeotropic blends, using the bubble pressure for saturation temperature overstates superheat by the temperature glide (11.1°F for R-407C, 14.0°F for R-454C, 22.1°F for R-455A). This calculator does dew-curve math automatically.
- Reading SH before steady state. Run at least 15 minutes after start before reading[1].
Underlying math
Formula
Superheat (°F) = T_suction_line − T_sat(P_suction) T_sat is read off the DEW curve at the measured suction pressure for zeotropic blends. For pure refrigerants and azeotropes, bubble ≡ dew, so the curve choice is moot.
Related tools
Subcooling Calculator
Companion to superheat on the liquid line. Together they pin down a system's charge state.
Combined PT / SH / SC
All three measurements on one form with pattern-matching diagnostic banner.
PT Calculator
Raw saturation-pressure lookup for any refrigerant.
System Diagnostic
Pattern matcher for high/low pressure × high/low SH/SC fingerprints.
Target Superheat Chart
Fixed-orifice target lookup by indoor WB × outdoor DB. Refrigerant-independent method.
R-410A Superheat Chart
Target matrix + R-410A saturation quick table for fixed-orifice residential AC.
R-22 Superheat Chart
Target matrix + R-22 saturation quick table for legacy fixed-orifice service.
High Suction Low Head
Diagnostic tree for the specific pattern where both pressures converge — internal leakage.
AC Low Side Pressure Too High
Diagnostic tree for suction above normal.
Low Suction Pressure
Broad diagnostic tree for suction below normal — undercharge, restriction, or airflow.
AC Compressor Short Cycling
Cycling patterns and their root causes on residential and automotive systems.
R-410A reference
Full PT chart, operating pressures, and lubricant guidance for the dominant residential AC refrigerant.
Frequently asked questions
›What is superheat?
Superheat is the temperature of refrigerant vapor above its saturation temperature at the same pressure. Title 24 measures it on the suction line near the suction service valve: suction-line temperature minus the saturation temperature at the suction pressure.[1] Copeland links low superheat to valve-plate, piston and connecting-rod damage, and liquid floodback to bearing wear from diluted oil.[8][9]
›What is the target superheat for an HVAC system?
Depends on the metering device. Fixed-orifice systems: a target from 5 to 45°F, read from Title 24's chart of indoor wet-bulb and outdoor dry-bulb[1]. TXV systems: typically 8–12°F, up to 15°F on high-TD coils; the valve holds a nearly constant superheat[3][4]. Walk-in coolers: 6–8°F (Sporlan) or 6–10°F at a 10°F design TD (Heatcraft); walk-in freezers: 4–6°F (Sporlan)[3][5]. For heat pumps, American Standard approves checking the charge only in cooling mode[6]. Always cross-check against the manufacturer's service literature for the specific equipment[3].
›How do I measure superheat in the field?
Connect a gauge to the suction service port and read the pressure in psig. Clamp a temperature sensor to the suction line near the suction service valve, in good contact with the line, and run the system in cooling for at least 15 minutes.[1] Convert the pressure to saturation temperature with your refrigerant's PT chart, using the dew point for blends, and subtract it from the line temperature.[2] This calculator does the conversion.
›What does low superheat indicate?
Low superheat means the evaporator is close to flooding. Sporlan lists a TXV that overfeeds and lost air movement from dirt or ice among the causes[11]; on a fixed-orifice system, compare with the chart target before adjusting the charge[1]. Liquid reaching the compressor damages it: Copeland lists valve-plate, piston and connecting-rod damage, and bearing wear from diluted oil[8][9]. Cross-check with subcooling and verify indoor airflow before adjusting charge.
›What does high superheat indicate?
High superheat means the evaporator is starved: above the chart target on a fixed-orifice system, or above the manufacturer's figure (Title 24's default limit is 25°F) on a TXV system[1]. A low charge raises superheat and lowers subcooling and evaporator pressure, and a liquid-line restriction such as a clogged filter-drier can starve the valve even with a proper charge[10]. Check subcooling first. Low subcooling alongside high superheat strongly suggests undercharge[10]. Verify indoor airflow and check the liquid line and filter-drier for a restriction[10] before adding refrigerant.
›Why does superheat math differ for zeotropic blends?
Zeotropic blends such as R-407C, R-454C and R-455A boil across a temperature range at constant pressure, so by the suction line the right reference is the dew point.[2] Reading the bubble point instead overstates superheat by the glide: 11.1°F for R-407C, 14.0°F for R-454C and 22.1°F for R-455A at a 40°F dew point, from the site's PT data. This calculator uses the dew point automatically.
›Is this the same as Total Superheat versus Evaporator Superheat?
This calculator works out superheat wherever you measure it. Title 24 reads it on the suction line near the suction service valve[1], while a TXV controls superheat at its bulb on the evaporator outlet.[3] Superheat at the compressor inlet runs higher: Sporlan's worked example reads 10°F at the bulb and 30°F at the compressor inlet.[7]
›Does this calculator work with R-1234yf and R-454B?
Yes. R-1234yf and R-454B are both in the calculator's list of 56 refrigerants.