HVAC PT ChartsVerified saturation data · 61 refrigerants

Superheat & Subcooling Fundamentals

Complete reference for HVAC technicians: what superheat and subcooling are, how to measure them in the field, what their target values mean for different system types, and how to use the pair together to diagnose charge and system issues.

TL;DR: Superheat tells you how thoroughly the evaporator boils the refrigerant. Subcooling tells you how thoroughly the condenser condenses it. Together they pin down whether a system is correctly charged, overcharged, undercharged, or has an airflow / metering device problem. Targets depend on the metering device (TXV vs fixed-orifice) and the application.

1. What superheat and subcooling are

Superheat is the temperature of refrigerant vapor above its saturation temperature at the same pressure. It is measured on the suction line. If the vapor at the suction port reads 60°F and the saturation temperature corresponding to the suction pressure is 45°F, superheat = 60 − 45 = 15°F.

Subcooling is the temperature of liquid refrigerant below its saturation temperature at the same pressure. It is measured on the liquid line. If the liquid at the condenser outlet reads 100°F and the saturation temperature corresponding to the discharge pressure is 112°F, subcooling = 112 − 100 = 12°F.

Both are non-negative on a working system. Negative superheat means liquid is reaching the compressor (slugging); negative subcooling means vapor is forming in the liquid line (flash gas at the metering device). Both are damaging conditions that require immediate diagnosis.

Superheat and subcooling on the PT diagramTemperature →Pressure →LIQUID(above saturation curve)VAPOR(below saturation curve)suction satSUPERHEATdischarge satSUBCOOLING

Superheat and subcooling on the PT diagram: vapor superheats above the saturation curve (suction-side measurement), liquid subcools below the saturation curve (condenser-side measurement). Source: ASHRAE Handbook of Refrigeration 2022 Ch. 1 (vapor-compression cycle).

2. How to measure superheat and subcooling in the field

For superheat:

  1. Connect the manifold gauge to the suction service port. Read suction pressure in PSIG.
  2. Clamp a contact temperature probe to the suction line within 6 inches of the compressor (or per the equipment OEM's specified measurement point). Insulate the probe from ambient air.
  3. Let the system run 10-15 minutes under load to stabilize. Record the probe temperature.
  4. Convert the suction pressure to saturation temperature for the refrigerant in the system — use the PT calculator, the superheat calculator (does the math), or a printed PT chart.
  5. Subtract saturation T from measured T. The difference is superheat.

For subcooling — same procedure on the liquid line:

  1. Read the discharge (high-side) pressure from the manifold.
  2. Clamp a probe to the liquid line at the condenser outlet (the smaller, uninsulated copper line). Insulate.
  3. Convert the liquid pressure to saturation temperature.
  4. Subtract measured T from saturation T. The difference is subcooling.

For zeotropic blends — R-407C, R-454C, R-455A, R-448A, R-449A — use the dewcurve for superheat and the bubblecurve for subcooling. The site's calculators handle this automatically. Using a single curve for both introduces an error equal to the temperature glide (11-22°F depending on blend).

3. Target values by system type

Target SH and SC by system type
System typeTarget SHTarget SCCharged by
Fixed-orifice residential AC5-25°FinformationalSH (ACCA Manual T chart)
TXV residential AC8-15°F8-12°FSC (OEM nameplate)
EEV residential AC5-15°F5-12°FSC + EEV diagnostic
Heat pump (cooling mode)8-15°F8-15°FSC
Heat pump (heating mode)10-20°F8-15°FSC at indoor coil
Walk-in cooler MT (TXV)6-12°F5-15°FSC
Walk-in freezer LT (TXV)8-15°F5-15°FSC
Centrifugal chiller2-5°F at evap2-5°F at condOEM-specific
Mobile AC (R-1234yf, R-134a)5-15°F5-10°FBy weight (SAE J639)
Hermetic compressor min (AHRI 540)≥20°FProtection floor
Target SH (blue) and SC (purple) by application (°F)051015202530Residential TXVSHSCResidential FXOSHSC informational on fixed-orificeHeat pump coolingSHSCHeat pump heatingSHSCWalk-in MTSHSCWalk-in LTSHSCChillerSHSCMobile ACSHSC

Target SH (blue) and SC (purple) ranges by application. Compressor minimums (AHRI 540) are protection thresholds at the compressor inlet, typically higher than service-line targets due to suction-line pickup. Source: ACCA Manual T (2017), ASHRAE Handbook of Refrigeration 2022 Ch. 23, AHRI Standard 540-2020, OEM service literature.

4. Diagnostic patterns — what each combination means

Four common SH × SC patterns, each pointing to a different root cause family. These are the foundation of refrigerant-side diagnostic work and underpin the eight-pattern matrix used in the combined diagnostic calculator.

Four-pattern SH × SC matrix
SHSCRoot causeVerification step
NormalNormalProperly chargedNo action — document baseline
HighLow / NegUnderchargeLeak search → repair → recharge by weight
Low / ZeroHighOverchargeVerify condenser airflow → recover in increments
HighHighRestriction OR low evap airflowFilter-drier check, evap airflow, TXV inspect
LowLowTXV stuck open OR sizing mismatchTXV diagnosis, sensing bulb inspection
SH × SC diagnostic pattern matrixTarget zone010203040-10010203040Superheat (°F)Subcooling (°F)Properly chargedUnderchargeOverchargeRestrictionTXV stuck open

The four-pattern matrix visualized in the SH × SC plane. Each quadrant corresponds to a different root cause family. The center region (8-15°F SH and 8-12°F SC for TXV residential) is the "properly charged" window. Source: ACCA Manual T (2017), ASHRAE Handbook of Refrigeration 2022 Ch. 23.

5. Worked service scenarios

Five field scenarios showing how SH and SC together drive service decisions. Each maps measured readings to a diagnostic verdict and specific service action.

1
Service problemR-410A (TXV)

Properly-charged R-410A residential AC

Scenario · 3-ton R-410A TXV residential AC, 95°F outdoor, 75°F return air, 63°F indoor WB. System has been running 15 minutes at steady state.

Measured
Suction P
130 PSIG
Suction line
60°F
Discharge P
380 PSIG
Liquid line
100°F
Saturation lookup (R-410A)
130 PSIG45°F satevap saturation
380 PSIG111°F satcond saturation
Derived
Superheat = 60°F − 45°F = 15°Fin 8-15°F TXV target
Subcooling = 111°F − 100°F = 11°Fin 8-12°F TXV target
OK · Properly charged — no service action
Both SH and SC inside target ranges; system is operating correctly. Document baseline values for future comparison and sign off.
2
Service problemR-410A (TXV)

Undercharge fingerprint — high SH + low SC

Scenario · Same R-410A TXV system, six months later. Customer reports weak cooling on a 95°F day. You take readings to confirm what's going on.

Measured
Suction P
100 PSIG
Suction line
70°F
Discharge P
320 PSIG
Liquid line
108°F
Derived
Superheat = 70°F − 31°F = 39°Fvery high (target 8-15°F)
Subcooling = 99°F − 108°F = −9°Fnegative — flash gas
Action required · Undercharge — leak somewhere in the system
High SH + negative SC is the textbook undercharge fingerprint. Refrigerant has leaked out since commissioning. Both pressures depressed below normal for ambient.
Fix
Find and repair the leak per EPA Section 608, then evacuate to 500 microns and charge by weight to nameplate. Don't add refrigerant without leak repair.
3
Service problemR-410A (TXV)

Overcharge fingerprint — low SH + high SC

Scenario · R-410A TXV system after a service add by a previous tech. The compressor is running noticeably louder and the customer's electric bill is up.

Measured
Suction P
160 PSIG
Suction line
55°F
Discharge P
480 PSIG
Liquid line
90°F
Derived
Superheat = 55°F − 55°F = 0°Fzero — slugging risk
Subcooling = 130°F − 90°F = 40°Fvery high — overcharge
Action required · Overcharge — liquid is reaching the compressor
Zero SH + 40°F SC is the classic overcharge fingerprint. Excess refrigerant backs up in the condenser (high SC) and saturated liquid reaches the compressor (zero SH); the noise is hydraulic events from incompressible liquid.
Fix
Recover refrigerant in 1 oz increments using a recovery / charging scale. Re-test SH and SC after each. Stop when SH = 8-15°F and SC = 8-12°F. If SH stays low after recovery, suspect TXV stuck open.
4
Service problemR-410A (TXV)

Restriction — high SH + high SC

Scenario · R-410A TXV system. Customer reports the AC isn't cooling as well as last summer. SH is high but SC is also high — not the typical undercharge pattern.

Measured
Suction P
100 PSIG
Suction line
75°F
Discharge P
400 PSIG
Liquid line
98°F
Derived
Superheat = 75°F − 31°F = 44°Fvery high
Subcooling = 115°F − 98°F = 17°Fhigh — refrigerant trapped
Investigate · Liquid-line restriction
High SH + high SC = restriction in the liquid line (clogged filter-drier, TXV stuck partly closed, kinked line). Refrigerant is in the system (high SC proves the condenser is filling) but can't reach the evaporator (high SH from evap starvation).
Fix
Check filter-drier outlet temperature — significant drop across the drier (e.g., 10°F colder than inlet) confirms restriction. Replace drier. If symptoms persist, inspect TXV operation and check line set for kinks. Don't add refrigerant — it won't fix a restriction.
5
Service problemR-454C (LT walk-in)

R-454C low-temp walk-in — dew curve for SH, bubble for SC

Scenario · R-454C low-temp walk-in freezer (-20°F evap target, 95°F ambient). R-454C is zeotropic with ~14°F glide — curve selection critical.

Measured
Suction P
7 PSIG
Suction line
5°F
Discharge P
200 PSIG
Liquid line
82°F
Saturation lookup (R-454C zeotropic)
7 PSIG dew−20°FUSE for SH
7 PSIG bubble−34°Fwrong for SH
200 PSIG bubble88°FUSE for SC
200 PSIG dew74°Fwrong for SC
Derived (correct curves)
SH (dew) = 5°F − (−20°F) = 25°Fhigh end LT range 8-15°F
SC (bubble) = 88°F − 82°F = 6°Fin 5-15°F LT range
Investigate · Slightly elevated SH — investigate TXV / charge
Correctly calculated using dew for SH and bubble for SC. SH is high end of the target range; SC is fine. Likely TXV slightly over-throttling, or slight undercharge. Wrong-curve calculation would have shown SH = 39°F (false alarm) and SC = −8°F (false alarm).
Fix
For zeotropic blends always verify curve selection in PT chart software. The dew curve at suction pressure for superheat; bubble curve at discharge pressure for subcooling. The site's calculators handle this automatically.

6. Common pitfalls

  1. Probing without insulation. Ambient air at the probe location pulls the reading toward room temperature — inflates apparent SH, depresses apparent SC. Always insulate the probe.
  2. Measuring before stabilization. Pressures and temperatures swing during startup and load changes. Wait 10-20 minutes under stable load before recording values.
  3. Wrong saturation curve on zeotropic blend. Using a single bubble or dew curve for both SH and SC on R-407C / R-454C / R-455A introduces an error equal to the glide (11-22°F) — enough to invalidate charging decisions.
  4. Assuming charge is the answer. Airflow, metering device condition, condenser cleanliness, indoor coil cleanliness, and load can all cause SH/SC to read off-target. Verify those before adjusting charge.
  5. Reading the wrong port. Suction is the LOW-side port on the larger insulated line. Discharge is the HIGH-side port on the smaller uninsulated line. Reversed connections invert the diagnosis entirely.
  6. Adjusting charge on a TXV using superheat. TXV systems hold SH near the valve setpoint regardless of charge. Subcooling is the primary metric on TXV / EEV systems.
  7. Confusing total vs evaporator superheat. Total SH (at compressor inlet, what charging procedures use) is 2-5°F higher than evap SH (what TXV bulb senses). ACCA Manual T targets are total SH.

7. FAQ

Why do I need both superheat and subcooling?

Each one alone tells half the story; together they pin down the system's charge state and isolate root causes. The classic patterns: high superheat + low subcooling = undercharge; low superheat + high subcooling = overcharge; both abnormal in the same direction = airflow or metering device issue. No single measurement gives you these patterns — you need both.

Which is the primary charging metric?

Depends on the metering device. Fixed-orifice systems are charged by superheat (per ACCA Manual T charging chart, indexed on indoor wet-bulb and outdoor dry-bulb). TXV / EEV systems are charged by subcooling (typically 8-12°F per OEM nameplate). On a TXV system the superheat hovers near the TXV setpoint regardless of charge, so superheat reads in-range even at overcharge — subcooling is the primary metric.

What's the difference between total superheat and evaporator superheat?

Total superheat is measured at the suction line near the compressor — what most charging procedures reference. Evaporator superheat is measured at the evaporator outlet, before any temperature pickup along the suction line. Total is usually 2-5°F higher than evaporator due to suction-line heat gain. ACCA Manual T charging charts target Total SH; TXV setpoints control to Evaporator SH.

How does temperature glide affect superheat measurement on zeotropic blends?

Significantly. On R-407C (~11°F glide) using the bubble curve gives a value that's ~11°F too high; on R-454C (~14°F glide) the error is ~14°F; on R-455A (~22°F) it's ~22°F. The site's calculators use the dew curve at suction pressure for SH automatically. Always verify your PT chart software does the right curve for the right side.

What does negative superheat mean?

Liquid refrigerant is reaching the compressor (slugging or flooding). Liquid is incompressible and damages compressor valves and bearings. Stop the system and diagnose before continuing. Common causes: overcharge, stuck-open TXV flooding the evaporator, severely low indoor airflow keeping the evap cold enough to flood.

What does negative subcooling mean?

Vapor bubbles are forming in the liquid line (flash gas). The metering device receives a two-phase mix instead of fully-liquid refrigerant; cooling capacity drops sharply. Causes: significant undercharge, restriction at filter-drier or expansion device, or non-condensables. The system is impaired; diagnose before adding refrigerant under EPA Section 608.

What's the AHRI 540 minimum return-gas superheat?

AHRI Standard 540 (Positive Displacement Refrigerant Compressors) specifies minimum return-gas superheat at the compressor suction: 20°F for hermetic compressors and 30°F for semi-hermetic compressors. These are compressor-protection minimums, not service-charging targets. A residential split system charged to 10°F TXV SH at the line measurement point still satisfies AHRI 540 because suction-line pickup adds further superheat between the line probe and the compressor crankcase.

How do approach temperatures relate to SH and SC?

Condenser approach = T_sat_discharge − T_ambient (15-25°F normal residential). Evaporator approach = T_return_air − T_sat_suction (20-40°F normal residential). They give a third dimension beyond SH and SC: a condenser-fouling case shows high SC AND high condenser approach (distinguishing it from overcharge which shows high SC + normal approach). The system pressure diagnostic calculator uses approach temperatures alongside SH/SC for richer fingerprint matching.

Superheat Calculator

Suction PSIG + line °F → SH with diagnostic banner.

Subcooling Calculator

Liquid PSIG + line °F → SC.

Combined SH / SC / PT

Both readings + eight-pattern diagnostic matrix.

Sources

  • ACCA Manual T (2017) — "Air-Side and Refrigerant-Side Diagnostics", target SH ranges and charging procedures
  • ASHRAE Handbook of Refrigeration 2022 — Chapters 1, 23 (vapor-compression cycle, service procedures)
  • ASHRAE Handbook of Fundamentals 2021 — vapor-compression cycle thermodynamics
  • AHRI Standard 540-2020 — Positive Displacement Refrigerant Compressors, minimum return-gas SH
  • EPA Section 608 (40 CFR Part 82 Subpart F) — refrigerant handling, leak repair requirements
  • CoolProp 7.2.0 (Bell et al. 2014, doi:10.1021/ie4033999) — saturation property source for site calculators
  • Equipment manufacturer service literature — Carrier, Trane, Lennox, Daikin, Goodman charging procedures