HVAC PT Charts

What Pressure Should R-454B Be?

Updated October 26, 2026

R-454B A2L Lower toxicity, lower flammability

EPA lists R-454B for new residential air conditioners and heat pumps.[21] Of the Carrier, Trane, Rheem, York and Lennox R-454B documents we checked, only Lennox's EL18KSLV instructions give a pressure table by outdoor temperature. Lennox does, for its EL18KSLV heat pump, and that is the source for this page.

The numbers below are charge-mode pressures, read with the unit forced to full capacity for a charge check, not the pressures a system shows in ordinary operation. Treat them as a charging reference, and confirm against the unit's own label.

Lennox's EL18KSLV heat pump instructions list R-454B pressures by outdoor temperature, measured in the unit's charge mode. At 95°F outdoors they show 138–142 psig vapor (low side) and 322–351 psig liquid (high side) for the ‑024 and ‑036 sizes. Lennox labels these charge-mode values, not normal operating pressures.[1]

R-454B pressures by outdoor temperature (charge mode)

R-454B charge-mode operating pressures by outdoor temperature, for the −024 and −036 sizes
Outdoor-024 low side-024 high side-036 low side-036 high side
65°F 18°C137 psig 945 kPa202 psig 1,393 kPa133 psig 917 kPa224 psig 1,544 kPa
70°F 21°C137 psig 945 kPa221 psig 1,524 kPa133 psig 917 kPa244 psig 1,682 kPa
75°F 24°C138 psig 951 kPa240 psig 1,655 kPa134 psig 924 kPa265 psig 1,827 kPa
80°F 27°C139 psig 958 kPa261 psig 1,800 kPa135 psig 931 kPa286 psig 1,972 kPa
85°F 29°C138 psig 951 kPa275 psig 1,896 kPa134 psig 924 kPa306 psig 2,110 kPa
90°F 32°C140 psig 965 kPa298 psig 2,055 kPa136 psig 938 kPa324 psig 2,234 kPa
95°F 35°C142 psig 979 kPa322 psig 2,220 kPa138 psig 951 kPa351 psig 2,420 kPa
100°F 38°C144 psig 993 kPa349 psig 2,406 kPa140 psig 965 kPa375 psig 2,586 kPa
105°F 41°C145 psig 1,000 kPa374 psig 2,579 kPa141 psig 972 kPa402 psig 2,772 kPa
110°F 43°C146 psig 1,007 kPa394 psig 2,717 kPa142 psig 979 kPa420 psig 2,896 kPa
115°F 46°C147 psig 1,014 kPa420 psig 2,896 kPa143 psig 986 kPa449 psig 3,096 kPa
R-454B charge-mode operating pressures by outdoor temperature, for the −024 and −036 sizes — Lennox EL18KSLV installation instructions, Table 6.

Lennox EL18KSLV installation instructions 508700-01 (12/2024), Table 6, within ±10 psig liquid and ±5 psig vapor, at an indoor airflow of 800 SCFM (‑024) and 1,050 SCFM (‑036). The ‑048/‑060 column is left out: as printed, its pressures fall as the outdoor temperature rises.[1]

What charge mode is

A DIP switch on the display board puts the unit in charge mode. Lennox has start-up and testing done at 100% capacity; after 10 minutes, the subcooling shown on the display is compared with the target for the indoor unit in its Table 4, and refrigerant is added if it reads low or recovered if it reads high.[1]

What the pressures mean in temperature

At 95°F outdoors, the 138–142 psig vapor range is a 53.6–55.2°F dew point and the 322–351 psig liquid range a 104.8–111.1°F bubble point, 10–16°F above the outdoor air.[16] See the R-454B PT chart.

R-454B vs R-410A and R-32

At 95°F outdoors:

Refrigerant and basisLow sideHigh side
R-454B, Lennox EL18KSLV, charge mode, 2 sizes138–142 psig322–351 psig[1]
R-410A, Lennox tables, 37 units134–151 psig336–404 psig[2][3][4][5][6][7]
R-410A, Goodman (80°F/67°F) and Lennox, 63 units134–155 psig329–413 psig[8][9][10][2][3][4][5][6][7]
R-32, Goodman and Amana (80°F/67°F), 26 units131–153 psig348–453 psig[11][12][13][14][15]

At equal saturation temperatures R-454B runs below both: at a 45°F dew point, R-454B is 118 psig against 130 psig for R-410A and 133 psig for R-32; at a 110°F bubble point, 346, 366 and 375 psig.[16]

Standing pressure (system off)

With the system off long enough for pressures to equalize, the gauges read the saturation pressure of the liquid refrigerant at its temperature; for a blend held as liquid in a closed container, Arkema gives the liquid (bubble) pressure as the one that applies.[17] During the off cycle, refrigerant migrates toward the coldest part of the system, so the reading follows that spot's temperature rather than the outdoor air.[18] NIST notes that non-condensable gas can be diagnosed from its partial pressure while the system is off.[19]

Standing pressure with the system off and equalized
Off temperatureStanding (psig / kPa)
65°F 18.3°C175 psig 1,209 kPa
70°F 21.1°C191 psig 1,313 kPa
75°F 23.9°C206 psig 1,424 kPa
80°F 26.7°C223 psig 1,540 kPa
85°F 29.4°C241 psig 1,663 kPa
90°F 32.2°C260 psig 1,793 kPa
95°F 35.0°C280 psig 1,930 kPa
100°F 37.8°C301 psig 2,074 kPa
105°F 40.6°C323 psig 2,225 kPa
110°F 43.3°C346 psig 2,385 kPa
115°F 46.1°C370 psig 2,552 kPa
Standing pressure with the system off and equalized — Computed from the CoolProp 7.2.0 pressure–temperature dataset.

Readings that point to a problem

Faults show up as a pattern across suction, head pressure, superheat and subcooling, compared with the same system running normally.[19] NIST measured these patterns on a 2.5-ton R-410A heat pump with a TXV in cooling mode, and its report also reproduces Breuker and Braun's chart for a rooftop unit with a fixed orifice.[19]

FaultSuctionHeadSuperheatSubcooling
Undercharge, superheat still under 16°Fno change detectedlowerno change detectedlower
Undercharge, superheat above 16°Flowerlowerhigherlower
Overchargeno change detectedhigherno change detectedhigher
Liquid-line restriction, superheat above 16°Flowerlowerhigherhigher
Low indoor airflowlowerlowerno change detectedno change detected
Low outdoor airflow, superheat under 16°Fhigherhigherno change detectedlower
Low outdoor airflow, superheat above 16°Flowerhigherhigherlower
Compressor valve leakagehigherlowerno change detectedlower
TXV system: each reading against normal operation (NIST SP 1087, Table 5.2)[19]

NIST split its results at 9°C (16.2°F) of superheat, where the TXV runs out of control range. A liquid-line restriction caused no detectable change below that point. Overcharge, low indoor airflow and compressor leakage never pushed superheat past it at the fault levels tested.[19]

FaultSuctionHeadSuperheatSubcooling
Refrigerant leak (undercharge)lowerlowerhigherlower
Liquid-line restrictionlowerlowerhigherhigher
Condenser fault (blocked coil)higherhigherlowerlower
Evaporator faultlowerlowerlowerlower
Compressor valve leakagehigherlowerlowerlower
Fixed-orifice system: Breuker and Braun's chart for a rooftop air conditioner with a short-tube orifice, as reproduced in NIST SP 1087, Table 5.1(a)[19]

Neither NIST chart covers an overcharged fixed-orifice system. DOE's flowchart below does.

DOE's order of checks

DOE's Building America diagnostics guide works through the readings in order once the indoor coil's temperature split runs more than 3°F below its target, with separate charts for fixed-orifice and TXV systems.[20]

ReadingFixed orificeTXV
Condensing temperature too far above outdoor airNon-condensables, fouled condenser coil, overcharge or liquid-line restrictionSame
Evaporator saturation temperature too lowLiquid-line restriction, fouled evaporator coil or low chargeSame, or the TXV is out of adjustment
Low subcooling, low superheatExpansion device overfeed or fouled evaporator coilTXV overfeed: unsecured bulb or adjustment
Low subcooling, high superheatUnderchargeUndercharge, or TXV underfeed: bad power element or adjustment
High subcooling, low superheatOverchargeOvercharge, or TXV overfeed
High subcooling, high superheatLow outdoor temperatureUndercharge, or TXV underfeed

DOE gives its limits as starting points. Its Table 3 lists a maximum condensing-over-ambient of 25°F above 12 SEER, 30°F at 10–12 SEER and 35°F below 10 SEER, and a minimum evaporator saturation temperature of 35°F, 40°F and 45°F alongside indoor wet bulbs of 62–63°F, 64–65°F and 66–67°F.[20] It adds that non-condensables or a liquid-line restriction also raise subcooling.[20]

Frequently asked questions

What's the normal operating pressure of R-454B at 95°F outdoor?

Lennox's EL18KSLV charge-mode table lists 138–142 psig vapor and 322–351 psig liquid at 95°F; Lennox labels these charge-mode values, not normal operating pressures.[1]

How does R-454B compare to R-410A?

At equal saturation temperatures R-454B sits below R-410A: 118 vs 130 psig at a 45°F dew point and 346 vs 366 psig at a 110°F bubble point.[16] Lennox's own R-410A tables run 134–151 psig suction and 336–404 psig liquid at 95°F.[2][3][4][5][6][7]

How does R-454B compare to R-32?

At equal saturation temperatures R-454B sits below R-32: 118 vs 133 psig at a 45°F dew point and 346 vs 375 psig at a 110°F bubble point.[16]

Can I use R-410A recovery equipment for R-454B?

Lennox's EL18KSLV instructions call for recovery equipment suitable for flammable refrigerants where applicable, with its electrical components sealed against ignition, and say not to mix refrigerants in recovery units or cylinders.[1]

How is the charge checked on an R-454B heat pump?

In charge mode, Lennox runs the unit at 100% capacity, then after 10 minutes compares the subcooling on the display with the target in its Table 4, adding refrigerant if it reads low or recovering if it reads high.[1]

How these numbers are calculated

The pressure table on this page is Lennox's charge-mode Table 6 for the EL18KSLV, extracted from the PDF by script and checked against the page image.[1]

The ‑048/‑060 column is left out because its printed liquid and vapor pressures fall as the outdoor temperature rises, which the other two sizes and basic physics do not.[1]

Saturation-temperature conversions and the standing-pressure table come from the site's R-454B pressure–temperature data (CoolProp 7.2.0).[16]

Sources

  1. [1]
    Elite Series EL18KSLV Units installation instructions 508700-01. Lennox. 12/2024. https://www.lennox.com/dA/9ab528c680/508700-01.pdf (accessed October 20, 2026). Table 6. Charge Mode Operating Pressures, PDF p. 26 — R-454B charge-mode liquid and vapor pressures by outdoor temperature.
  2. [2]
    Elite Series XC13 Units installation instructions 506635-01. Lennox. 09/11. https://www.lennox.com/dA/1ac2b167d5/Lennox_XC13_IOM.pdf (accessed October 20, 2026). Table 4. Normal Operating Pressures, PDF p. 26 — R-410A typical liquid and suction/vapor operating pressures by outdoor temperature.
  3. [3]
    Merit Series 14ACX Units installation instructions 506645-01. Lennox. 07/11. https://www.lennox.com/dA/8b22f61eb8/Lennox_14ACX_IOM.pdf (accessed October 20, 2026). Table 4. HFC-410A Normal Operating Pressures, PDF p. 27 — R-410A typical liquid and suction/vapor operating pressures by outdoor temperature.
  4. [4]
    XC21 Series Units service literature Corp. 0504-L2. Lennox. 07/2009. https://tech.lennoxintl.com/C03e7o14l/VIu12Ch2uV/0504g.pdf (accessed October 20, 2026). Table 10. Normal Operating Pressures, PDF p. 18 — R-410A typical liquid and suction/vapor operating pressures by outdoor temperature.
  5. [5]
    Elite Series XP16 Units installation instructions 506640-01. Lennox. 12/10. https://www.lennox.com/lib/legacy-res/pdfs/installation_maintenance/lennox_xp16_iom.pdf (accessed October 20, 2026). Table 7. Normal Operating Pressures, PDF p. 29 — R-410A typical liquid and suction/vapor operating pressures by outdoor temperature.
  6. [6]
    XP17 System installation instructions 506586-01. Lennox. 06/11. https://www.lennox.com/lib/legacy-res/pdfs/installation_maintenance/lennox_xp17_iom.pdf (accessed October 20, 2026). Table 10. Normal Operating Pressure, PDF p. 31 — R-410A typical liquid and suction/vapor operating pressures by outdoor temperature.
  7. [7]
    Merit Series 13HPX Units installation instructions 506727-01. Lennox. 06/11. https://www.lennox.com/dA/138cce8866/Lennox_13HPX_IOM.pdf (accessed October 20, 2026). Table 4. Normal Operating Pressures, PDF p. 27-28 — R-410A typical liquid and suction/vapor operating pressures by outdoor temperature.
  8. [8]
    GSX14 Split System Air Conditioner, up to 15 SEER (spec sheet SS-GSX14). Goodman. 1/19. https://apps.goodmanmfg.com/brochures/files/5c5085ab40be5SS-GSX14.pdf (accessed October 20, 2026). Expanded Cooling Data — R-410A liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  9. [9]
    GSX16 Split System Air Conditioner (spec sheet SS-GSX16). Goodman. 3/21. https://apps.goodmanmfg.com/brochures/files/6062166241d6dSS-GSX16.pdf (accessed October 20, 2026). Expanded Cooling Data — R-410A liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  10. [10]
    DSXC18 Split System Air Conditioner, up to 18 SEER (spec sheet SS-DSXC18). Goodman. 11/16. https://apps.goodmanmfg.com/brochures/files/582b1bf6dd15bSS-DSXC18.pdf (accessed October 20, 2026). Expanded Cooling Data — R-410A liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  11. [11]
    GXV6S Variable-Speed R-32 Split System Air Conditioner, up to 17.2 SEER2 (spec sheet SS-GXV6S-R32). Goodman. 07/25. https://apps.goodmanmfg.com/brochures/files/68ed3c631108aSS-GXV6S-R32.pdf (accessed October 20, 2026). Expanded Cooling Data — R-32 liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  12. [12]
    GXV9S Variable-Speed R-32 Split System Air Conditioner, up to 19 SEER2 (spec sheet SS-GXV9S-R32). Goodman. 07/25. https://apps.goodmanmfg.com/brochures/files/68ed3d136d70fSS-GXV9S-R32.pdf (accessed October 20, 2026). Expanded Cooling Data — R-32 liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  13. [13]
    AXV9S Variable-Speed R-32 Split System Air Conditioner, up to 19 SEER2 (spec sheet SS-AXV9S-R32). Amana. 07/25. https://apps.goodmanmfg.com/brochures/files/68ee8aca01ff7SS-AXV9S-R32.pdf (accessed October 20, 2026). Expanded Cooling Data — R-32 liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  14. [14]
    AZV9S Variable-Speed R-32 Split System Heat Pump, up to 21.0 SEER2 (spec sheet SS-AZV9S-R32). Amana. 09/25. https://apps.goodmanmfg.com/brochures/files/68ee8c439a303SS-AZV9S-R32.pdf (accessed October 20, 2026). Expanded Cooling Data — R-32 liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  15. [15]
    AZV7S Variable-Speed R-32 Split System Heat Pump, up to 19.0 SEER2 (spec sheet SS-AZV7S-R32). Amana. 07/25. https://apps.goodmanmfg.com/brochures/files/68ee8e7c8878dSS-AZV7S-R32.pdf (accessed October 20, 2026). Expanded Cooling Data — R-32 liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  16. [16]
    CoolProp 7.2.0. CoolProp (I. H. Bell, J. Wronski, S. Quoilin, V. Lemort). https://coolprop.org/ (accessed October 2, 2026). Bell, I. H.; Wronski, J.; Quoilin, S.; Lemort, V. Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp. Ind. Eng. Chem. Res. 53, 2498–2508 (2014). https://doi.org/10.1021/ie4033999
  17. [17]
    Liquid or Vapor Pressure: Which One Do You Need for Your Application? Arkema (Forane). https://forane.arkema.com/en/resources/tech-tips/liquid-or-vapor-pressure/ (accessed October 20, 2026). which saturation pressure (liquid/bubble vs vapor/dew) applies to a blend held as liquid in a closed container.
  18. [18]
    Scroll compressors SH090 to SH485, R410A: Application guidelines, AB243586442172en-US1301. Danfoss. https://assets.danfoss.com/documents/90219/AB243586442172en-US1301.pdf (accessed October 20, 2026). p. 31, off-cycle migration — refrigerant migrates to the coldest part of the system during the off cycle.
  19. [19]
    NIST Special Publication 1087, Cooling Mode Fault Detection and Diagnosis Method for a Residential Heat Pump (M. Kim, S. H. Yoon, W. V. Payne, P. A. Domanski). National Institute of Standards and Technology. October 2008. https://nvlpubs.nist.gov/nistpubs/Legacy/SP/nistspecialpublication1087.pdf (accessed October 20, 2026). Table 5.1(a) p. 40 and Table 5.2 p. 41, fault-direction charts; Section 5.4.1 p. 58 — residential heat-pump cooling-mode fault patterns.
  20. [20]
    Measure Guideline: Air Conditioner Diagnostics, Maintenance, and Replacement (D. Springer, B. Dakin), NREL/SR-5500-56283. U.S. DOE Building America. March 2013. https://www1.eere.energy.gov/buildings/publications/pdfs/building_america/measure_guide_air_cond_diagnostics.pdf (accessed October 20, 2026). Section 3.4 pp. 32–33, Table 3 p. 32, Figures 17–18 p. 33 — order-of-checks diagnostic flowcharts for fixed-orifice and TXV systems.
  21. [21]
    U.S. EPA, Fact Sheet — Final Rule 23: Protection of Stratospheric Ozone: New Listings for the Significant New Alternatives Policy Program. U.S. EPA. April 23, 2021. https://www.epa.gov/sites/default/files/2021-04/documents/fact_sheet_snap_final_rule_23_final_4-23-21_508.pdf (accessed October 25, 2026). Listing table, end use 'Residential and light commercial air conditioning and heat pumps (New)' — SNAP lists these A2Ls for new equipment only (R-32: same, excluding self-contained room air conditioners).

Related