Superheat Calculator

Enter your suction-line pressure and temperature for any refrigerant; get superheat plus diagnostic context. Correct dew-curve math for zeotropic blends so high-glide refrigerants (R-407C, R-454C, R-455A) don't read 11-22°F off.

Updated September 29, 2026

Temp
Pressure
Superheat Enter your suction-line pressure and temperature, then click Calculate.
Target superheat reference

Target superheat depends on the metering device. These ranges are general guidance; always defer to the equipment manufacturer's charging procedure.

System typeTarget superheatReference
Fixed orifice (residential AC)8–25°F (chart-based)OEM fixed-orifice charging charts
TXV (residential / commercial AC)8–15°F (often 10°F setpoint)Manufacturer spec
EXV8–15°F (controlled to setpoint)Equipment controls
Refrigeration — medium temp10–20°FASHRAE Refrigeration Handbook 2022
Refrigeration — low temp10–20°F at evap; higher across suction lineASHRAE Refrigeration Handbook 2022

For fixed-orifice systems use the manufacturer's charging chart with outdoor dry-bulb and indoor wet-bulb temperatures rather than a single setpoint. See Carrier R-410A charging chart for an example.

Chart range for R-410A: −40°F to 150°F.

Measurement locations for superheat on a split-system HVACSimplified split-system HVAC layout showing an outdoor condensing unit on the left connected by a two-pipe line set (upper suction line, lower liquid line) to an indoor A-coil and return-air grille on the right. Probe callouts indicate where the technician places the pipe-clamp thermometer, manifold gauge, and (for superheat) wet-wick psychrometer to measure the values needed for a target-superheat or target-subcooling charge check.SH = T_suction − T_sat(P_suction)Outdoor condensing unitsuction (vapor)liquidIndoor coilReturn grilleTPWB
Wet-wick psychrometer at the return grille; pipe-clamp thermometer on the suction line near the outdoor service valve; manifold gauge on the suction port. Superheat = suction-line temperature minus saturation temperature at the measured suction pressure.

What superheat is and why we measure it

Superheat is the temperature of refrigerant vapor above its saturation temperature at the same pressure. At any pressure, the saturation temperature is the boundary where liquid and vapor coexist; once the refrigerant has fully boiled, every degree above that saturation reading is one degree of superheat.

On a working HVAC system, suction-line superheat serves two simultaneous purposes. First, it protects the compressor: positive superheat guarantees no liquid is reaching the suction crankcase (liquid refrigerant in the cylinder is essentially incompressible — "slugging" damages valves, bearings, and rotors). Second, it tells you whether the evaporator is being fed correctly — too little superheat means liquid is leaving the evaporator unboiled (wasted capacity); too much means the evaporator is starved.

Where to measure suction-line superheatEvaporator(refrigerant boils)indoor airflow ↓suction line (vapor)Compressor(suction inlet)thermocouplewithin 6" of inlet, insulatedmanifold portread suction P here · convert to T_satSuperheat = T_line (yellow probe) − T_sat (from purple port pressure)

Schematic of a residential split-system suction line, showing where the thermocouple should clamp (within 6 inches of the compressor inlet, insulated from ambient) and where the suction pressure is read at the manifold service port. Source: Carrier / Trane / Lennox residential service literature.

Superheat answers a single question
How much vapor margin do you have above saturation? Positive margin = safe for the compressor and the evaporator's capacity is mostly used; near-zero margin = slugging risk; very high margin = the evaporator is starved.

Two metering devices, two different questions

What you do with a superheat reading depends entirely on whether the system uses a fixed-orifice metering device (piston, capillary tube, accurator) or a thermostatic expansion valve (TXV / EEV). Different devices, different procedures.

Fixed-orifice vs TXV vs EEV
Metering deviceCharge byVerify byTypical SH
Fixed orifice (piston, captube)Superheat (target from chart)Match fixed-orifice chart target5-25°F (variable)
TXV (thermostatic expansion valve)Subcooling (charge to SC target)Steady SH at TXV setpoint8-15°F (regulated)
EEV (electronic expansion valve)SubcoolingEEV control board diagnostic5-15°F (regulated)

Fixed-orifice devices have no feedback control — superheat varies with charge, ambient, and indoor load. Charging a fixed-orifice system means adjusting refrigerant mass until superheat lands on the fixed-orifice charging-chart target value for the current indoor wet bulb / outdoor dry bulb conditions. TXV and EEV systems have a sensing element that modulates flow to maintain a fixed superheat setpoint (typically 10°F at the bulb).

On TXV / EEV systems, charge is set by subcooling instead. Superheat measurement on these systems verifies the valve is operating in its target range; it does not determine charge directly. A TXV system reading 30°F superheat usually points to a stuck-closed valve or restriction, not undercharge (cross-check subcooling).

Target superheat reference — fixed-orifice charging charts and OEM service literature

The fixed-orifice charging chart targets superheat based on the indoor wet-bulb temperature entering the evaporator coil and the outdoor dry-bulb temperature at the condenser. Higher indoor WB and lower outdoor DB both raise the target. The interactive matrix below computes the target from a field-approximation formula; the chart or label on the specific unit always takes precedence.

Interactive lookup — target superheat

Measured at the return-air grille with a wet-wick psychrometer. Typical cooling: 60–72°F WB.

Shaded thermometer near the condenser. Design condition: 95°F.

Target superheat
13°F
TSH = round((3 × 67 − 80 − 95) / 2) = 13°F
WB \ DB55°F 60°F 65°F 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F
50°F 85———————————
52°F 1186——————————
54°F 141196—————————
56°F 17141297————————
58°F 20171512107———————
60°F 23201815131085—————
62°F 2623211816131186————
64°F 292624211916141196———
66°F 32292724221917141297——
68°F 35323027252220171512107—
70°F 3835333028252320181513108
72°F 41383633312826232118161311
74°F 44413936343129262421191614
76°F 47444239373432292724221917

— = target below 5°F; superheat charging not recommended at these conditions. Industry convention on Trane and Carrier bead charts.

Standard field approximation of fixed-orifice charging charts (within about ±3°F of the Carrier/Bryant table in normal conditions; see California Title 24 Reference Appendix RA3.2, Table RA3.2-2). The chart or label on the unit always takes precedence.

Target superheat by application (OEM + ASHRAE)
ApplicationTarget SHSource
Residential AC, TXV / EEV8-15°FCarrier, Trane, Lennox, Daikin OEM literature
Residential AC, fixed orificeper chartfixed-orifice charging charts
Walk-in cooler (MT), TXV6-12°FASHRAE Handbook—Refrigeration (2022), “Charging & Testing”
Walk-in freezer (LT), TXV8-15°FASHRAE Handbook—Refrigeration (2022), “Charging & Testing”
Heat pump, heating mode10-20°FCarrier / Trane heat-pump service procedures
Centrifugal chiller at evap2-5°FASHRAE Handbook—HVAC Systems and Equipment (2024), “Liquid-Chilling Systems”
Target superheat by application (°F)05101520253035Chiller (evap)2-5Walk-in cooler MT6-12Residential TXV8-15Walk-in freezer LT8-15Heat pump heating10-20Residential FXO5-25Source: ASHRAE Handbook—Refrigeration (2022), OEM service literature.

Target superheat ranges across HVAC applications. Service-line targets are read at the suction line near the compressor; suction-line pickup adds further superheat between the line probe and the compressor crankcase.

Real service problems solved with the superheat measurement

Ten field scenarios spanning residential AC charging (fixed-orifice and TXV), walk-in commercial refrigeration with wide-glide zeotropic blends, heat pump heating mode, and slugging-risk pattern recognition. Each shows what gets measured, the PT chart lookup that converts suction pressure to saturation temperature, the superheat derivation, and a verdict on what to do.

1
Service problemR-410A (fixed orifice)

Charging a new R-410A residential AC by superheat target

Scenario · Brand-new R-410A residential AC, piston metering device, 95°F outdoor dry bulb, 63°F indoor wet bulb (75°F return air, 50% RH). You need to set the charge by superheat per the manufacturer's charging instructions, cross-checked against the fixed-orifice charging chart.

Measured at the manifold
Suction P
120 PSIG
Suction line
56°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
120 PSIG 40.7°F sat evaporator saturation
Derived
Superheat = 56.0 − 40.7 (dew) = 15.3°F in target 8-25°F
Target superheat (63°F WB / 95°F DB) = 7°F fixed-orifice charging-chart target
Investigate · Superheat above target — undercharged
Measured SH is 15.3°F vs the fixed-orifice charging-chart target of approximately 7°F at this WB / DB combination. Superheat above target means the evaporator is starved; the system is undercharged, and adding refrigerant will reduce superheat toward the target.
Fix
Add refrigerant in 2-4 oz increments using a scale, allowing 10-15 minutes for steady state between additions. Stop when SH = 7°F (±2°F tolerance). Confirm subcooling lands in the 8-12°F range as a sanity check on the final charge.
2
Service problemR-410A (TXV)

Verifying TXV operation on a commissioned R-410A system

Scenario · R-410A TXV-equipped residential AC, just commissioned. Charge was set by subcooling (10°F target). You want to verify the TXV is regulating superheat correctly before signing off.

Measured at the manifold
Suction P
130 PSIG
Suction line
60°F
Discharge P
380 PSIG
Liquid line
101°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
130 PSIG 45.0°F sat evaporator saturation
380 PSIG 112.7°F sat condenser saturation
Derived
Superheat = 60.0 − 45.0 (dew) = 15.0°F in target 8-15°F
Subcooling = 112.7 (bubble) − 101.0 = 11.7°F in target 8-12°F
OK · Within target ranges
Superheat (15.0°F) sits inside the 8-15°F TXV target window and subcooling (12.6°F, right at the top of the 8-12°F range) confirms the charge is correct. The valve is regulating properly. No further service action.
3
Service problemR-410A (TXV)

High superheat — diagnosing undercharge vs restriction

Scenario · Same R-410A TXV system, two months later. Customer reports poor cooling on a 95°F day. Suction pressure looks low and the suction line feels warmer than expected.

Measured at the manifold
Suction P
110 PSIG
Suction line
75°F
Discharge P
340 PSIG
Liquid line
100°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
110 PSIG 36.2°F sat evaporator saturation
340 PSIG 104.6°F sat condenser saturation
Derived
Superheat = 75.0 − 36.2 (dew) = 38.8°F above target 8-15°F
Subcooling = 104.6 (bubble) − 100.0 = 4.6°F below target 8-12°F
Investigate · Likely undercharge
High superheat with negative subcooling is the textbook undercharge fingerprint: the evaporator is starved (high SH) and the condenser is not maintaining a subcooled liquid column (negative SC, flash gas reaching the metering device). Two months from commissioning suggests a slow leak.
Fix
Find and repair the leak before recharging (leak-repair duties are size-based per 40 CFR 82.157 and 84.106; no blanket federal no-top-off rule). After repair, evacuate to 500 microns and charge by weight to nameplate using a recovery / charging scale. Re-test SH and SC at steady state.
4
Service problemR-410A (TXV)

Low superheat — overcharge or TXV flooding the evaporator

Scenario · R-410A TXV system after a service add by a previous tech. The compressor is running noticeably louder than normal and you suspect liquid floodback.

Measured at the manifold
Suction P
155 PSIG
Suction line
55°F
Discharge P
460 PSIG
Liquid line
100°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-410A)
155 PSIG 54.6°F sat evaporator saturation
460 PSIG 127.0°F sat condenser saturation
Derived
Superheat = 55.0 − 54.6 (dew) = 0.4°F below target 8-15°F
Subcooling = 127.0 (bubble) − 100.0 = 27.0°F above target 8-12°F
Investigate · Likely overcharge
Near-zero superheat with 35.0°F subcooling is the classic overcharge fingerprint: excess refrigerant backs up in the condenser (high SC) and saturated liquid is reaching the compressor (near-zero SH). Continued operation risks valve damage or hydraulic lock; the compressor noise is the warning sign.
Fix
Recover refrigerant in 1 oz increments using a recovery / charging scale. Re-test SH and SC after each step. Stop when SH = 8-15°F and SC = 8-12°F. If SH remains low after charge is correct, suspect TXV stuck open or sensing-bulb failure.
5
Service problemR-22 (TXV)

Zero superheat — emergency slugging shutdown

Scenario · Legacy R-22 split system reported as 'making knocking noise'. You arrive on-site, hook up gauges, and find concerning numbers. The compressor sound is consistent with hydraulic events.

Measured at the manifold
Suction P
80 PSIG
Suction line
48°F
Discharge P
245 PSIG
Liquid line
100°F
Ambient
95°F
Return air
75°F
PT chart lookup (R-22)
80 PSIG 47.5°F sat evaporator saturation
245 PSIG 115.7°F sat condenser saturation
Derived
Superheat = 48.0 − 47.5 (dew) = 0.5°F below target 8-15°F
Subcooling = 115.7 (bubble) − 100.0 = 15.7°F above target 8-12°F
Investigate · Likely overcharge
Near-zero superheat (0.5°F) means the suction line carries an essentially saturated liquid-vapor mixture; the compressor is actively slugging. Combined with 40.7°F subcooling (severe overcharge) this is an emergency: every minute of run-time is breaking valves and crankshaft bearings.
Fix
Shut the system down immediately. Recover refrigerant down to nameplate weight, inspect compressor for damage (oil analysis, crankcase oil sample), and consider adding a suction-line accumulator if not present. Verify TXV operation and indoor airflow before restarting. For R-22 service: the supply chain is past-tense — plan for retrofit (R-407C, R-422D) or full equipment replacement.
6
Service problemR-407C (zeotropic, ~11°F glide)

R-407C medium-temp commercial — why curve selection matters

Scenario · R-407C retrofit on a medium-temp commercial unit (reach-in deli case), 25°F evaporator target. R-407C is zeotropic with ~11°F glide, so the bubble vs dew distinction is significant for superheat calculation.

Measured at the manifold
Suction P
30 PSIG
Suction line
35°F
Ambient
95°F
PT chart lookup (R-407C)
30 PSIG dew 12.3°F sat evap outlet — use for superheat
30 PSIG bubble 0.5°F sat evap inlet — reference only
Derived
Superheat = 35.0 − 12.3 (dew) = 22.7°F above target 10-20°F
Investigate · High superheat
Using the dew curve (the correct curve for suction-line superheat on zeotropic blends) gives SH = 22.7°F, well above the 6-12°F MT walk-in target — the evaporator is starved, so check charge, TXV feed, and evaporator airflow. Using the bubble curve would have shown SH = 34.5°F, overstating superheat by the 11.7°F glide and pushing you to over-add refrigerant.
Fix
For zeotropic blends (R-407C, R-454C, R-455A, R-448A, R-449A), always confirm your PT chart software is using the dew curve at suction pressure. This calculator does it automatically. The glide-aware curve selection diagram below illustrates the principle.
7
Service problemR-454C (zeotropic, ~14°F glide)

R-454C low-temp walk-in freezer superheat charging

Scenario · R-454C walk-in freezer (low-temp commercial), −20°F target evaporator temperature, 95°F ambient. R-454C is a wide-glide zeotropic blend used as a low-GWP replacement for R-404A in commercial refrigeration.

Measured at the manifold
Suction P
5 PSIG
Suction line
0°F
Ambient
95°F
Box temp
−10°F
PT chart lookup (R-454C)
5 PSIG dew −24.4°F sat evap outlet — use for superheat
5 PSIG bubble −38.5°F sat evap inlet — reference only
Derived
Superheat = 0.0 − −24.4 (dew) = 24.4°F above target 10-20°F
Investigate · High superheat
24.4°F SH using the correct dew curve is above the 8-15°F LT target. Either the system is slightly undercharged, the TXV is slightly over-controlling, or the evaporator coil has reduced airflow. Cross-check subcooling and look for frost patterns on the evaporator before charging.
Fix
For R-454C LT systems, verify TXV is rated for LT service and the sensing bulb is properly insulated on the suction line. Glide-related stratification in the evaporator can shift TXV control behavior compared to R-404A, even though the target SH range is similar.
8
Service problemR-410A (heat pump, heating mode)

R-410A heat pump superheat at 35°F outdoor heating mode

Scenario · R-410A residential air-source heat pump in heating mode. 35°F outdoor (outdoor coil is now the evaporator), 70°F indoor return air (indoor coil is the condenser). Customer report of weak warm air — you're checking if the system is operating correctly.

Measured at the manifold
Suction P
80 PSIG
Suction line
30°F
Outdoor temp
35°F
Return air
70°F
PT chart lookup (R-410A)
80 PSIG 20.9°F sat evaporator saturation
Derived
Superheat = 30.0 − 20.9 (dew) = 9.1°F in target 8-15°F
Evaporator approach = 35.0 (outdoor) − 20.9 = 14.1°F outdoor coil runs below ambient to absorb heat
OK · Superheat in target range
9.1°F superheat sits just below the heating-mode 10-20°F target range; the TXV is regulating. Outdoor coil saturation at 20.9°F is 14.1°F below ambient — normal for heating mode where the evaporator must run below ambient to absorb heat from cold outdoor air.
Fix
If the customer reports weak heating despite normal SH, the issue is likely elsewhere: low refrigerant charge (cross-check SC), defrost cycle malfunction (frost blocking outdoor coil airflow), auxiliary heat strip not engaging, or improperly sized equipment for the climate. Verify auxiliary heat operation in cold weather.
9
Service problemR-134a (centrifugal chiller)

R-134a centrifugal chiller — very low superheat targets (2–5°F)

Scenario · Water-cooled R-134a centrifugal chiller, 45°F leaving chilled water, 85°F entering condenser water. You measure suction and want to verify the evaporator is operating correctly. Chillers are different from residential AC — much lower SH targets.

Measured at the manifold
Suction P
38 PSIG
Suction line
50°F
Entering water
85°F
Return air
75°F
PT chart lookup (R-134a)
38 PSIG 43.0°F sat evaporator saturation
Derived
Superheat = 50.0 − 43.0 (dew) = 7.0°F below target 8-25°F
Evaporator approach = 75.0 (return air) − 43.0 = 32.0°F in target 20-40°F
Investigate · Low superheat
7.0°F superheat is above the centrifugal chiller 2-5°F target. Chillers deliberately run very low SH: the flooded evaporator design maximizes heat transfer by submerging tubes in liquid refrigerant, and an eliminator section + accumulator prevents liquid carryover to the compressor. Superheat this high suggests the evaporator refrigerant level or float/level control is slightly low — the tight 2.0°F approach confirms the heat exchanger itself is clean, so investigate charge and level control rather than fouling.
10
Service problemR-32 / R-454B (A2L)

R-32 vs R-454B superheat targets — same as R-410A?

Scenario · New installation choosing between R-32 (pure) and R-454B (zeotropic ~2°F glide) for residential AC. Field tech asks: do these A2L refrigerants need different superheat targets than R-410A?

Result · R-32 vs R-454B superheat targets — same as R-410A?
R-32 and R-454B both use the same 8-15°F TXV target as R-410A — OEMs specify nearly identical service procedures. R-454B's 2°F glide is small enough that bubble vs dew rarely matters at residential operating pressures, but use the dew curve to be exact. This calculator handles R-454B's dew curve automatically.
Fix
For A2L-rated equipment (R-32, R-454B), follow IEC 60335-2-40 charge limit requirements based on room floor area and refrigerant flammability classification. Recovery and service equipment must be A2L-rated; service tools that handle R-410A are typically rated for these A2Ls as well, but verify before use.

Glide-aware curve selection — why dew is the right curve for superheat

Zeotropic blends boil across a temperature range at constant pressure. As liquid refrigerant enters the evaporator (bubble point) and progresses to fully vaporized (dew point), the saturation temperature rises by the glide value — even though the pressure is unchanged.

Suction-line superheat is measured downstream of the evaporator, where refrigerant is fully vaporized. The relevant saturation reference is the dew point: the temperature at which the last drop of liquid disappeared. Using the bubble point would treat the entry-side saturation as if it were the exit-side reference, overstating superheat by the glide value (bubble sits below dew, so subtracting it inflates the result).

R-407C — which curve for which measurement?−20020406080100120050100150200250Temperature (°F)Saturation pressure (PSIG)Dew (use for superheat)Bubble (use for subcooling)11°F glidebubble − dew at same P

R-407C bubble and dew saturation curves over the service range, showing the consistent 11°F glide between the two. Use the dew curve at suction pressure for superheat (suction line); use the bubble curve at discharge pressure for subcooling (liquid line). Source: CoolProp 7.2.0 saturation data for R-407C.

Glide values across common HVAC blends: R-454B ≈ 2°F, R-448A ≈ 11°F, R-449A ≈ 10°F, R-407C ≈ 11°F, R-454C ≈ 14°F, R-455A ≈ 22°F. Wrong-curve selection on R-455A would shift superheat by 22°F — easily enough to invalidate a charging decision or trigger an unnecessary compressor protection shutdown.

Six common superheat measurement mistakes

  1. Wrong curve on zeotropes. Using bubble pressure for saturation temperature on R-407C / R-454C / R-455A overstates superheat by the glide value (11-22°F). This calculator uses the dew curve automatically — verify any paper PT chart you reference shows both columns and use the dew column for SH.
  2. Thermocouple at the wrong location. Industry standard is within 6 inches of the compressor suction inlet on the suction line; the OEM service literature for your equipment specifies the exact location. Probing at the evaporator outlet, at random elbows mid-line, or at the compressor body itself gives different values that don't match the OEM's SH target.
  3. No insulation on the probe. An uninsulated clamp-on probe reads partly the line temperature and partly the ambient air temperature. Inside a warm attic this inflates apparent superheat by 5-10°F. Use closed-cell foam tape or insulation putty over the probe.
  4. Reading before steady state. Superheat takes 10-20 minutes after compressor start to stabilize as the system reaches steady-state operation. Brief after-start spikes or transient values during defrost / cycle changes are not charging-decision data.
  5. Confusing total vs evaporator superheat. Total Superheat is measured at the compressor suction (what manifold-based service procedures use); Evaporator Superheat is at the evap outlet (what the TXV bulb senses). Total SH is 2-5°F higher than Evap SH due to suction-line pickup. Fixed-orifice charging-chart targets are Total SH; TXV setpoints are Evap SH.
  6. PSIG vs PSIA mix-up. Service gauges read PSIG (gauge pressure above atmospheric); some refrigerant property software wants PSIA (absolute, measured from vacuum). PSIA = PSIG + 14.696 at sea level. Confusing the two shifts the saturation lookup by 15 PSI which can swing a reading by 5°F or more at low-side pressures.

When to use this calculator vs the others

  • Superheat Calculator (this page) — suction-line measurement. Charge fixed-orifice systems; verify TXV operation; diagnose evaporator-side issues (undercharge, restriction, flooding).
  • Subcooling Calculator — liquid-line measurement. Charge TXV / EEV systems; diagnose condenser-side issues (fouling, overcharge, low ambient airflow). Always pair with SH.
  • Combined SH / SC / PT — both sides plus pattern-matching diagnostic banner. Use for full system commissioning or comprehensive diagnostic.
  • PT Calculator — raw saturation lookup, no measurement input. Reference tool for cross-checking or comparing refrigerants.
  • System Pressure Diagnostic — high-low pressure × high-low SH / SC pattern matcher. Use when you have all four values and want a quick fingerprint identification (undercharge, overcharge, restriction, airflow problem, compressor issue).

Primary sources behind the calculator and content

  • CoolProp 7.2.0 (Bell, Wronski, Quoilin, Lemort 2014, doi:10.1021/ie4033999) — REFPROP-compatible Helmholtz EOS for all saturation temperatures.
  • California Title 24 Reference Appendix RA3.2 (Table RA3.2-2) — the field-approximation target-superheat table for fixed-orifice charging (indexed on indoor wet-bulb and outdoor dry-bulb). The chart or label on the specific unit always takes precedence over this approximation.
  • ASHRAE Handbook—Refrigeration (2022) — vapor-compression cycle fundamentals and “Equipment and System Dehydrating, Charging, and Testing” (service procedures and target superheat by application). The reference text for commercial refrigeration service.
  • ASHRAE Handbook—HVAC Systems and Equipment (2024) — “Liquid-Chilling Systems” (centrifugal chiller evaporator approach and superheat targets).
  • EPA Section 608 (40 CFR Part 82 Subpart F) — Refrigerant-handling certification and size-based leak-repair duties (40 CFR 82.157); no blanket rule bars adding refrigerant to a leaking system.
  • OEM service literature — Carrier, Trane, Lennox, Daikin, Mitsubishi, Goodman charging procedures and target superheat ranges per equipment model.
  • IEC 60335-2-40 (2022) — A2L refrigerant charge limits and installation requirements for R-32, R-454B equipment.

How to read your results

Superheat (°F or °C)
How many degrees the suction-line vapor sits above its saturation temperature — the vapor margin that keeps liquid out of the compressor. Roughly 5–25°F covers most working systems (TXV/EEV target 8–15°F; fixed-orifice varies by charging chart); near-zero means little margin against flooding, and a value well above 25°F points to a starved evaporator (undercharge, restriction, or low airflow).
Saturation temperature at suction pressure
The temperature the entered suction pressure corresponds to on the PT chart — the baseline the superheat is measured from (superheat = line temp − this value). For zeotropic blends the tool reads the dew curve (labeled as such), which is the correct boundary for suction-line superheat; using the bubble curve would overstate superheat by the refrigerant's glide.
Diagnostic banner
Interprets the reading against generic thresholds: negative superheat means liquid is reaching the compressor (slugging — stop and investigate); under 5°F is very low margin (suspect overcharge, a stuck TXV, or low evaporator load); 5–25°F is within the typical operating range; above 25°F is high (suspect undercharge, an over-controlling TXV, an airflow problem, or a liquid-line restriction). Always confirm against the equipment's charging chart or manufacturer spec.

How to use this calculator

  1. Pick the refrigerant in the system. Defaults to R-410A.
  2. Read the suction-line pressure from the low-side manifold gauge — most service gauges read PSIG by default.
  3. Measure the suction-line temperature with a contact or clamp-on probe within 6 inches of the compressor inlet. Insulate from ambient air and let the reading stabilize (10-20 min after compressor start).
  4. Enter both values. The calculator returns superheat in °F (or °C if you toggle the unit) plus a diagnostic banner.
  5. Compare against your equipment's target superheat (OEM charging chart, TXV spec, or the fixed-orifice charging-chart reference below).

Common errors

  • Reading the discharge pressure instead of the suction pressure. The suction is the LOW side; discharge is the HIGH side.
  • Probing the suction line without insulating — ambient air pulls the reading toward room temperature, inflating apparent superheat.
  • On zeotropic blends, using the bubble pressure for saturation temperature — overstates superheat by the temperature glide (11°F for R-407C, 14°F for R-454C, 22°F for R-455A). This calculator does dew-curve math automatically.
  • Forgetting that fixed-orifice and TXV systems have very different target ranges. A fixed-orifice system reading 10°F superheat on a 95°F day may actually be undercharged per the fixed-orifice charging chart.
  • Reading SH before steady state. Allow 10-20 minutes after compressor start before the readings stabilize.
Underlying math

Formula

Superheat (°F) = T_suction_line − T_sat(P_suction) T_sat is read off the DEW curve at the measured suction pressure for zeotropic blends. For pure refrigerants and azeotropes, bubble ≡ dew, so the curve choice is moot.

Source

Saturation temperatures from CoolProp 7.2.0 (Bell, Wronski, Quoilin, Lemort 2014, doi:10.1021/ie4033999), REFPROP-compatible Helmholtz EOS. Fixed-orifice target superheat is a field approximation of the OEM charging charts (see California Title 24 Reference Appendix RA3.2, Table RA3.2-2); application target ranges from the ASHRAE Handbook—Refrigeration (2022), “Equipment and System Dehydrating, Charging, and Testing”, and equipment-specific manufacturer charging charts (Carrier, Trane, Lennox, Daikin, Goodman).

Worked example

R-410A residential AC, 95°F outdoor, TXV metering: Suction pressure (gauge): 130 PSIG Suction-line temperature: 60°F Saturation temperature at 130 PSIG: 45°F (CoolProp 7.2.0) Superheat = 60 − 45 = 15°F Within the typical 8-15°F TXV target range and comfortably above the slugging threshold. For a fixed-orifice system, cross-check against the fixed-orifice charging chart for the specific indoor wet-bulb / outdoor dry-bulb combination.

Related tools

Frequently asked

›What is superheat?

Superheat is the temperature of refrigerant vapor above its saturation temperature at the same pressure. On a working HVAC system, it's measured at the suction line near the compressor: actual suction-line temperature minus the saturation temperature corresponding to the suction-line pressure. Positive superheat means the refrigerant has fully boiled; zero or negative superheat means liquid is reaching the compressor — slugging, which damages valves and bearings.

›What is the target superheat for an HVAC system?

Depends on the metering device. Fixed-orifice systems target a variable 5-25°F superheat read from a fixed-orifice charging chart indexed on indoor wet-bulb and outdoor dry-bulb temperatures (a field approximation of the OEM bead charts). TXV / EEV systems target a fixed 8-15°F superheat regardless of ambient (the valve regulates to its setpoint, typically 10°F). Walk-in coolers target 6-12°F; walk-in freezers 8-15°F; heat-pump heating mode 10-20°F. Always cross-check against the manufacturer's service literature for the specific equipment.

›How do I measure superheat in the field?

Connect a manifold gauge to the suction service port and read the pressure in PSIG. Clamp a contact temperature probe on the suction line within 6 inches of the compressor inlet, insulate it from ambient air, and let the reading stabilize (10-20 minutes after start). Convert the suction pressure to saturation temperature using a PT chart for your refrigerant — use the dew curve for zeotropic blends. Subtract: superheat = T_line − T_sat. This calculator does the conversion and dew-curve selection automatically.

›What does low superheat indicate?

Low superheat (under 5°F on most systems) usually means the system is overcharged, the metering device is flooding the evaporator (TXV stuck open, oversized orifice, missing distributor nozzle), or indoor airflow is too low to fully boil the refrigerant. Liquid refrigerant reaching the compressor — slugging — causes valve damage and bearing failure. Cross-check with subcooling and verify indoor airflow before adjusting charge.

›What does high superheat indicate?

High superheat (over 25°F on most residential systems) usually means undercharge, a liquid-line restriction starving the evaporator, a TXV over-controlling or stuck partially closed, or low indoor load. Check subcooling first — low subcooling alongside high superheat strongly suggests undercharge. Verify indoor airflow and inspect the filter-drier (a partially clogged drier raises subcooling on the inlet side and superheat at the outlet) before adding refrigerant.

›Why does superheat math differ for zeotropic blends?

Zeotropic blends (R-407C, R-454C, R-455A, R-448A, R-449A) condense and evaporate across a temperature range at constant pressure. On the suction line the refrigerant has already passed through evaporation — the relevant saturation boundary is the dew temperature, not the bubble temperature. This calculator uses the dew curve automatically for zeotropic blends. Using the bubble curve for R-407C would overstate superheat by approximately 11°F; for R-455A by approximately 22°F (bubble sits below dew at a given pressure, so subtracting it inflates the result).

›Is this the same as Total Superheat versus Evaporator Superheat?

This calculator computes superheat at the measurement point — typically the suction line near the compressor, which is the 'Total Superheat' value most charging procedures reference. Evaporator Superheat (at the evaporator outlet, before line pickup) is 2-5°F higher than Total Superheat at the compressor. TXV setpoints control to Evaporator Superheat; fixed-orifice charging charts target Total Superheat. The distinction matters most on systems with long suction line sets exposed to warm spaces.

›Does this calculator work with R-1234yf and R-454B?

Yes — R-1234yf (mobile AC) and R-454B (residential AC A2L replacement for R-410A) are both supported, along with the full 49 CoolProp-modeled refrigerants in the dataset. For R-454B (zeotropic, ~2°F glide) the calculator uses the dew curve automatically, though the glide is small enough that bubble vs dew rarely changes the SH reading by more than 2-3°F. R-1234yf is pure and uses a single saturation curve.

Data sources & provenance

All saturation calculations use the verified refrigerant dataset (CoolProp 7.2.0, HEOS backend + named manufacturer datasheets for unmodeled blends).

This calculator is provided as a reference. Always verify pressure values against the equipment data plate and manufacturer service literature before charging or troubleshooting a specific system. Saturation pressure differs from operating pressure; see superheat & subcooling fundamentals.