HVAC PT Charts

What Pressure Should R-22 Be?

Updated October 26, 2026

R-22 A1 Lower toxicity, no flame propagation

You have gauges on an older home air conditioner and a suction and liquid-line number you cannot quite place. The equipment makers published a running pressure for each R-22 unit, and that is what the ranges here come from.

Call a normal reading a fault and you remove or add refrigerant that was fine; miss a real fault and the compressor pays for it. Either mistake is expensive on a system you can no longer top off casually.

At 95°F outdoors, Goodman and Lennox tables list a running R-22 air conditioner at 73–85 psig suction (low side) and 212–258 psig liquid (high side), read at the service valves.[1][2][3] That spans 21 outdoor units, with Goodman's at 80°F/67°F indoor air.[1][2][3] Your unit's nameplate and charging information carry its own values.[2]

R-22 running pressures by outdoor temperature

Suction is read at the suction service valve and liquid at the liquid service valve. Each row spans every manufacturer table for that outdoor temperature.[1][2][3]

Operating pressure by outdoor temperature, from manufacturer tables
OutdoorLow side (suction)High side (liquid)
65°F 18°C65–79 psig 448–545 kPa130–178 psig 896–1,227 kPa
75°F 24°C70–81 psig 483–558 kPa156–199 psig 1,076–1,372 kPa
85°F 29°C72–82 psig 496–565 kPa175–227 psig 1,207–1,565 kPa
95°F 35°C73–85 psig 503–586 kPa212–258 psig 1,462–1,779 kPa
105°F 41°C75–89 psig 517–614 kPa239–291 psig 1,648–2,006 kPa
115°F 46°C82–92 psig 565–634 kPa264–331 psig 1,820–2,282 kPa
Operating pressure by outdoor temperature, from manufacturer tables — Goodman spec sheets and Lennox installation instructions

Goodman SS-GSC13 (5/15) covers 7 units at 80°F/67°F indoor air, three airflows each. Lennox 13ACD (505,366M, 01/08) covers 7 units with TXV and fixed-orifice tables, and Lennox HS26 (504,672M, 04/04) 7 more; HS26 lists no 115°F row, so that row draws on 21 tables instead of 28. Lennox lists values within ±10 psig liquid and ±5 psig suction.[1][2][3]

Every unit at 95°F (28 tables)

Goodman rows are at 80°F/67°F indoor air and the middle of the three listed airflows.

MakerModelTypeLow side (psig)High side (psig)Source
GoodmanGSC130181G*single-stage83226SS-GSC13 p. 5
GoodmanGSC130241F*single-stage81233SS-GSC13 p. 7
GoodmanGSC130301**single-stage81256SS-GSC13 p. 9
GoodmanGSC130361G*single-stage83245SS-GSC13 p. 11
GoodmanGSC130421C*single-stage84219SS-GSC13 p. 13
GoodmanGSC130481C*single-stage84220SS-GSC13 p. 15
GoodmanGSC130601D*single-stage80219SS-GSC13 p. 17
Lennox13ACD-018TXV8221913ACD 505,366M p. 18
Lennox13ACD-024TXV8323613ACD 505,366M p. 18
Lennox13ACD-030TXV7923313ACD 505,366M p. 18
Lennox13ACD-036TXV8325213ACD 505,366M p. 18
Lennox13ACD-042TXV8124113ACD 505,366M p. 18
Lennox13ACD-048TXV8022913ACD 505,366M p. 18
Lennox13ACD-060TXV8024313ACD 505,366M p. 18
Lennox13ACD-018fixed orifice (RFC)8221813ACD 505,366M p. 18
Lennox13ACD-024fixed orifice (RFC)8223213ACD 505,366M p. 18
Lennox13ACD-030fixed orifice (RFC)7923713ACD 505,366M p. 18
Lennox13ACD-036fixed orifice (RFC)8324713ACD 505,366M p. 18
Lennox13ACD-042fixed orifice (RFC)8224013ACD 505,366M p. 18
Lennox13ACD-048fixed orifice (RFC)8022713ACD 505,366M p. 18
Lennox13ACD-060fixed orifice (RFC)8123913ACD 505,366M p. 18
LennoxHS26-018not stated78223HS26 504,672M p. 14
LennoxHS26-024not stated79226HS26 504,672M p. 14
LennoxHS26-030not stated76223HS26 504,672M p. 14
LennoxHS26-036not stated73223HS26 504,672M p. 14
LennoxHS26-042not stated78227HS26 504,672M p. 14
LennoxHS26-048not stated75216HS26 504,672M p. 14
LennoxHS26-060not stated76232HS26 504,672M p. 14

R-22 head pressure: what pushes it up

The high-side gauge on a split system reads liquid-line pressure at the liquid service valve, and it follows the outdoor temperature. From 65°F to 115°F outdoors, it rose 121–176 psig across these tables.[1][2]

Indoor humidity adds to it: in Goodman's tables at 95°F, raising the entering wet bulb from 59°F to 71°F raised liquid pressure 35–41 psig.[1]

Carrier lists a dirty condenser coil, a failed fan motor and condenser air recirculation as causes of high pressure, and its R-22 units open the high-pressure switch around 400 psig.[5] DOE's diagnostic guide adds overcharge, non-condensables and a liquid-line restriction when the condensing temperature runs too far above outdoor air.[6]

R-22 suction pressure: indoor load and outdoor temperature

Suction rises with the wet bulb of the air entering the indoor coil. In Goodman's tables at 95°F outdoors and an 80°F indoor dry bulb, raising the wet bulb from 59°F to 71°F raised suction 17–18 psig on each unit.[1]

Suction and liquid pressure by entering indoor wet bulb, at 95°F outdoors and 80°F indoor dry bulb
Indoor wet bulbLow side (suction)High side (liquid)
59°F66–73 psig 455–503 kPa187–227 psig 1,289–1,565 kPa
63°F71–78 psig 490–538 kPa201–244 psig 1,386–1,682 kPa
67°F77–85 psig 531–586 kPa212–258 psig 1,462–1,779 kPa
71°F82–91 psig 565–627 kPa222–269 psig 1,531–1,855 kPa
Suction and liquid pressure by entering indoor wet bulb, at 95°F outdoors and 80°F indoor dry bulb — Goodman expanded cooling data

Outdoor temperature moved suction about as much in Goodman's tables, 17–18 psig from 65°F to 115°F. Lennox's tables moved less: 5–10 psig with a TXV and 12–20 psig with a fixed orifice, and HS26, listed only to 105°F, rose 4–6 psig.[1][2][3]

Across the three airflows Goodman lists, suction changed 3–4 psig and liquid 8–10 psig at 95°F.[1]

What the pressures mean in temperature

At 95°F outdoors, the 73–85 psig suction range is a 43.0–50.6°F saturation temperature, and the 212–258 psig liquid range is 105.4–119.4°F, 10–24°F above the outdoor air.[4] See the R-22 PT chart.

Standing pressure with the system off

With the system off long enough for the pressures to equalize, the gauges read the saturation pressure of the liquid refrigerant at its temperature. During the off cycle, refrigerant migrates toward the coldest part of the system, so the reading follows that spot's temperature rather than the outdoor air.[7] NIST notes that non-condensable gas can be diagnosed from its partial pressure while the system is off.[8]

Standing pressure with the system off and equalized
Off temperatureStanding (psig / kPa)
65°F 18.3°C111 psig 767 kPa
70°F 21.1°C121 psig 837 kPa
75°F 23.9°C132 psig 912 kPa
80°F 26.7°C144 psig 990 kPa
85°F 29.4°C156 psig 1,073 kPa
90°F 32.2°C168 psig 1,161 kPa
95°F 35.0°C182 psig 1,253 kPa
100°F 37.8°C196 psig 1,351 kPa
105°F 40.6°C211 psig 1,453 kPa
110°F 43.3°C226 psig 1,561 kPa
115°F 46.1°C243 psig 1,674 kPa
Standing pressure with the system off and equalized — Computed from the CoolProp 7.2.0 pressure–temperature dataset.

Servicing an R-22 system today

US production and import of HCFC-22 ended January 1, 2020 under the EPA Class II ozone-depleting-substance phaseout.[10] Recover the charge and repair leaks rather than topping off.

Readings that point to a problem

Faults show up as a pattern across suction, head pressure, superheat and subcooling, compared with the same system running normally.[8] NIST measured these patterns on a 2.5-ton R-410A heat pump with a TXV in cooling mode, and its report also reproduces Breuker and Braun's chart for a rooftop unit with a fixed orifice.[8]

FaultSuctionHeadSuperheatSubcooling
Undercharge, superheat still under 16°Fno change detectedlowerno change detectedlower
Undercharge, superheat above 16°Flowerlowerhigherlower
Overchargeno change detectedhigherno change detectedhigher
Liquid-line restriction, superheat above 16°Flowerlowerhigherhigher
Low indoor airflowlowerlowerno change detectedno change detected
Low outdoor airflow, superheat under 16°Fhigherhigherno change detectedlower
Low outdoor airflow, superheat above 16°Flowerhigherhigherlower
Compressor valve leakagehigherlowerno change detectedlower
TXV system: each reading against normal operation (NIST SP 1087, Table 5.2)[8]

NIST split its results at 9°C (16.2°F) of superheat, where the TXV runs out of control range. A liquid-line restriction caused no detectable change below that point. Overcharge, low indoor airflow and compressor leakage never pushed superheat past it at the fault levels tested.[8]

FaultSuctionHeadSuperheatSubcooling
Refrigerant leak (undercharge)lowerlowerhigherlower
Liquid-line restrictionlowerlowerhigherhigher
Condenser fault (blocked coil)higherhigherlowerlower
Evaporator faultlowerlowerlowerlower
Compressor valve leakagehigherlowerlowerlower
Fixed-orifice system: Breuker and Braun's chart for a rooftop air conditioner with a short-tube orifice, as reproduced in NIST SP 1087, Table 5.1(a)[8]

Neither NIST chart covers an overcharged fixed-orifice system. DOE's flowchart below does.

DOE's order of checks

DOE's Building America diagnostics guide works through the readings in order once the indoor coil's temperature split runs more than 3°F below its target, with separate charts for fixed-orifice and TXV systems.[6]

ReadingFixed orificeTXV
Condensing temperature too far above outdoor airNon-condensables, fouled condenser coil, overcharge or liquid-line restrictionSame
Evaporator saturation temperature too lowLiquid-line restriction, fouled evaporator coil or low chargeSame, or the TXV is out of adjustment
Low subcooling, low superheatExpansion device overfeed or fouled evaporator coilTXV overfeed: unsecured bulb or adjustment
Low subcooling, high superheatUnderchargeUndercharge, or TXV underfeed: bad power element or adjustment
High subcooling, low superheatOverchargeOvercharge, or TXV overfeed
High subcooling, high superheatLow outdoor temperatureUndercharge, or TXV underfeed

DOE gives its limits as starting points. Its Table 3 lists a maximum condensing-over-ambient of 25°F above 12 SEER, 30°F at 10–12 SEER and 35°F below 10 SEER, and a minimum evaporator saturation temperature of 35°F, 40°F and 45°F alongside indoor wet bulbs of 62–63°F, 64–65°F and 66–67°F.[6] It adds that non-condensables or a liquid-line restriction also raise subcooling.[6]

Frequently asked questions

What should R-22 pressures be at 70, 80, 90 and 100°F?

Lennox's 13ACD tables list R-22 in 5°F steps: at 70°F, 67–80 psig suction and 148–174 psig liquid; at 80°F, 73–81 and 174–201 psig; at 90°F, 77–82 and 203–233 psig; at 100°F, 80–84 and 234–271 psig.[2]

What is normal R-22 head pressure?

At 95°F outdoors, 212–258 psig on the liquid line in Goodman and Lennox tables, rising to 264–331 psig at 115°F.[1][2][3] Carrier's R-22 units open the high-pressure switch around 400 psig.[5]

What is R-22 standing pressure?

With the system off and equalized, it is R-22's saturation pressure at the refrigerant's temperature: about 132 psig at 75°F and 182 psig at 95°F.[4]

What should R-22 suction pressure be?

73–85 psig at 95°F outdoors in manufacturer tables, 65–79 psig at 65°F and 82–92 psig at 115°F.[1][2][3]

Can you still recharge a system with R-22?

Yes, but no new R-22 is produced: US production and import ended January 1, 2020.[10] Repair leaks and recover the charge rather than topping off.

How these numbers are calculated

Every operating range on this page comes from manufacturer tables, extracted from the PDFs by script rather than retyped, checked for consistent trends and spot-checked against the page images.

Goodman's SS-GSC13 spec sheet lists liquid ("Hi PR") and suction ("Lo PR") pressure at the service valves for each outdoor unit at four indoor dry bulbs (70–85°F), four wet bulbs (59–71°F), three airflows and six outdoor temperatures. We use the 80°F/67°F rows, the indoor conditions of the AHRI 210/240 AFull rating test (95°F outdoors), unless a section says otherwise.[9]

Lennox's 13ACD (with separate TXV and fixed-orifice tables) and HS26 manuals list typical pressures by outdoor temperature without stating indoor conditions. Saturation temperatures and standing pressures come from CoolProp 7.2.0.[1][2][3][4]

Sources

  1. [1]
    GSC13 Split System Air Conditioner, 13 SEER, R-22 (spec sheet SS-GSC13). Goodman. 5/15. https://apps.goodmanmfg.com/brochures/files/5711345664158SS-GSC13.pdf (accessed October 20, 2026). Expanded Cooling Data — R-22 liquid (Hi PR) and suction (Lo PR) pressures at the service valves, by outdoor temperature and indoor condition.
  2. [2]
    Merit Series 13ACD Units installation instructions 505,366M. Lennox. 01/08. https://www.lennox.com/dA/b1e4c32104/Lennox_13ACD_IOM.pdf (accessed October 20, 2026). Table 6. HCFC-22 Normal Operating Pressures, PDF p. 18 — R-22 typical liquid and suction/vapor operating pressures by outdoor temperature.
  3. [3]
    HS26 Series Units installation instructions 504,672M. Lennox. 04/04. https://www.lennox.com/dA/f9fb3f7ce3/Lennox_HS26_IOM.pdf (accessed October 20, 2026). Table 5. Normal Operating Pressures, PDF p. 14 — R-22 typical liquid and suction/vapor operating pressures by outdoor temperature.
  4. [4]
    CoolProp 7.2.0. CoolProp (I. H. Bell, J. Wronski, S. Quoilin, V. Lemort). https://coolprop.org/ (accessed October 2, 2026). Bell, I. H.; Wronski, J.; Quoilin, S.; Lemort, V. Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp. Ind. Eng. Chem. Res. 53, 2498–2508 (2014). https://doi.org/10.1021/ie4033999
  5. [5]
    Residential Air Conditioners and Heat Pumps Using R-22 and Puron Refrigerant: Application Guideline and Service Manual, Catalog No. 24-25-2SM. Carrier. 04/08. https://www.shareddocs.com/hvac/docs/1009/Public/07/24-25-2SM.pdf (accessed October 20, 2026). p. 13, High-Pressure Switch — high-pressure-switch cutout settings and high-head causes.
  6. [6]
    Measure Guideline: Air Conditioner Diagnostics, Maintenance, and Replacement (D. Springer, B. Dakin), NREL/SR-5500-56283. U.S. DOE Building America. March 2013. https://www1.eere.energy.gov/buildings/publications/pdfs/building_america/measure_guide_air_cond_diagnostics.pdf (accessed October 20, 2026). Section 3.4 pp. 32–33, Table 3 p. 32, Figures 17–18 p. 33 — order-of-checks diagnostic flowcharts for fixed-orifice and TXV systems.
  7. [7]
    Scroll compressors SH090 to SH485, R410A: Application guidelines, AB243586442172en-US1301. Danfoss. https://assets.danfoss.com/documents/90219/AB243586442172en-US1301.pdf (accessed October 20, 2026). p. 31, off-cycle migration — refrigerant migrates to the coldest part of the system during the off cycle.
  8. [8]
    NIST Special Publication 1087, Cooling Mode Fault Detection and Diagnosis Method for a Residential Heat Pump (M. Kim, S. H. Yoon, W. V. Payne, P. A. Domanski). National Institute of Standards and Technology. October 2008. https://nvlpubs.nist.gov/nistpubs/Legacy/SP/nistspecialpublication1087.pdf (accessed October 20, 2026). Table 5.1(a) p. 40 and Table 5.2 p. 41, fault-direction charts; Section 5.4.1 p. 58 — residential heat-pump cooling-mode fault patterns.
  9. [9]
    AHRI Standard 210/240-2023 (2020), Performance Rating of Unitary Air-conditioning and Air-source Heat Pump Equipment. AHRI. 2023 (2020). https://www.ahrinet.org/system/files/2023-09/AHRI%20Standard%20210.240-2023%20%282020%29.pdf (accessed October 19, 2026)
  10. [10]
    Phaseout of Class II Ozone-Depleting Substances. US EPA. last updated April 1, 2026. https://www.epa.gov/ods-phaseout/phaseout-class-ii-ozone-depleting-substances (accessed October 2, 2026)

Related