R427A PT Chart
Updated October 12, 2026
R-427A
Quaternary HFC blend (15% R-32 / 25% R-125 / 10% R-143a / 50% R-134a). Branded as Arkema Forane 427A. ASHRAE A1, GWP 2,138. Marketed as 'simple retrofit' from R-22 — works with any of mineral, alkylbenzene, or POE oils.
R-427A saturation pressure splits across its glide: dew 61.2 PSIG at 40°F, bubble 216.2 PSIG at 100°F, and 113.7–134.7 PSIG dew-to-bubble at 70°F. Use the dew column for superheat and the bubble column for subcooling. The full table below runs from −40°F to 150°F in 1°F steps.
Not yet checked against an independent source.
- Temperature glide
- 10.5°F at a 40°F dew point[3]
R-427A PT chart — printable saturation table
Looking for the R-427A PT chart PDF for shop reference? The complete pressure-temperature saturation table is below: every 1° increment from −40°F to 150°F (or to the refrigerant's critical temperature). Use the Print / Save as PDF button in the table header to download a clean, table-only PDF (the rest of the page is hidden from the print output).
R-427A PT Chart — Pressure-Temperature Saturation Table
Computed with CoolProp 7.2.0 in 1°F steps · hvacptcharts.com
| Temp (°F) | Bubble (PSIG) | Dew (PSIG) |
|---|---|---|
| −40°F | 2.2 | 5.1 in. Hg vac. |
| −39°F | 2.7 | 4.4 in. Hg vac. |
| −38°F | 3.1 | 3.7 in. Hg vac. |
| −37°F | 3.6 | 3.0 in. Hg vac. |
| −36°F | 4.0 | 2.2 in. Hg vac. |
| −35°F | 4.5 | 1.4 in. Hg vac. |
| −34°F | 5.0 | 0.7 in. Hg vac. |
| −33°F | 5.5 | 0.1 |
| −32°F | 6.0 | 0.5 |
| −31°F | 6.5 | 0.9 |
| −30°F | 7.0 | 1.3 |
| −29°F | 7.6 | 1.7 |
| −28°F | 8.1 | 2.2 |
| −27°F | 8.7 | 2.6 |
| −26°F | 9.2 | 3.1 |
| −25°F | 9.8 | 3.5 |
| −24°F | 10.4 | 4.0 |
| −23°F | 11.0 | 4.5 |
| −22°F | 11.6 | 5.0 |
| −21°F | 12.2 | 5.5 |
| −20°F | 12.8 | 6.0 |
| −19°F | 13.5 | 6.5 |
| −18°F | 14.1 | 7.1 |
| −17°F | 14.8 | 7.6 |
| −16°F | 15.5 | 8.2 |
| −15°F | 16.2 | 8.8 |
| −14°F | 16.9 | 9.3 |
| −13°F | 17.6 | 9.9 |
| −12°F | 18.3 | 10.5 |
| −11°F | 19.0 | 11.1 |
| −10°F | 19.8 | 11.8 |
| −9°F | 20.6 | 12.4 |
| −8°F | 21.3 | 13.0 |
| −7°F | 22.1 | 13.7 |
| −6°F | 22.9 | 14.4 |
| −5°F | 23.7 | 15.1 |
| −4°F | 24.6 | 15.8 |
| −3°F | 25.4 | 16.5 |
| −2°F | 26.3 | 17.2 |
| −1°F | 27.1 | 17.9 |
| 0°F | 28.0 | 18.7 |
| 1°F | 28.9 | 19.4 |
| 2°F | 29.8 | 20.2 |
| 3°F | 30.8 | 21.0 |
| 4°F | 31.7 | 21.8 |
| 5°F | 32.7 | 22.6 |
| 6°F | 33.6 | 23.4 |
| 7°F | 34.6 | 24.3 |
| 8°F | 35.6 | 25.1 |
| 9°F | 36.7 | 26.0 |
| 10°F | 37.7 | 26.9 |
| 11°F | 38.7 | 27.8 |
| 12°F | 39.8 | 28.7 |
| 13°F | 40.9 | 29.7 |
| 14°F | 42.0 | 30.6 |
| 15°F | 43.1 | 31.6 |
| 16°F | 44.2 | 32.5 |
| 17°F | 45.4 | 33.5 |
| 18°F | 46.6 | 34.6 |
| 19°F | 47.7 | 35.6 |
| 20°F | 48.9 | 36.6 |
| 21°F | 50.2 | 37.7 |
| 22°F | 51.4 | 38.8 |
| 23°F | 52.6 | 39.9 |
| 24°F | 53.9 | 41.0 |
| 25°F | 55.2 | 42.1 |
| 26°F | 56.5 | 43.2 |
| 27°F | 57.8 | 44.4 |
| 28°F | 59.2 | 45.6 |
| 29°F | 60.5 | 46.8 |
| 30°F | 61.9 | 48.0 |
| 31°F | 63.3 | 49.2 |
| 32°F H₂O freeze | 64.7 | 50.5 |
| 33°F | 66.2 | 51.8 |
| 34°F | 67.6 | 53.1 |
| 35°F | 69.1 | 54.4 |
| 36°F | 70.6 | 55.7 |
| 37°F | 72.1 | 57.0 |
| 38°F | 73.7 | 58.4 |
| 39°F | 75.2 | 59.8 |
| 40°F | 76.8 | 61.2 |
| 41°F | 78.4 | 62.6 |
| 42°F | 80.0 | 64.1 |
| 43°F | 81.7 | 65.6 |
| 44°F | 83.4 | 67.1 |
| 45°F | 85.0 | 68.6 |
| 46°F | 86.7 | 70.1 |
| 47°F | 88.5 | 71.7 |
| 48°F | 90.2 | 73.2 |
| 49°F | 92.0 | 74.8 |
| 50°F | 93.8 | 76.4 |
| 51°F | 95.6 | 78.1 |
| 52°F | 97.5 | 79.7 |
| 53°F | 99.3 | 81.4 |
| 54°F | 101.2 | 83.1 |
| 55°F | 103.1 | 84.9 |
| 56°F | 105.1 | 86.6 |
| 57°F | 107.0 | 88.4 |
| 58°F | 109.0 | 90.2 |
| 59°F | 111.0 | 92.0 |
| 60°F | 113.0 | 93.9 |
| 61°F | 115.1 | 95.8 |
| 62°F | 117.2 | 97.7 |
| 63°F | 119.3 | 99.6 |
| 64°F | 121.4 | 101.5 |
| 65°F | 123.5 | 103.5 |
| 66°F | 125.7 | 105.5 |
| 67°F | 127.9 | 107.5 |
| 68°F | 130.2 | 109.6 |
| 69°F | 132.4 | 111.6 |
| 70°F | 134.7 | 113.7 |
| 71°F | 137.0 | 115.9 |
| 72°F | 139.3 | 118.0 |
| 73°F | 141.7 | 120.2 |
| 74°F | 144.1 | 122.4 |
| 75°F | 146.5 | 124.6 |
| 76°F | 148.9 | 126.9 |
| 77°F | 151.4 | 129.2 |
| 78°F | 153.9 | 131.5 |
| 79°F | 156.4 | 133.9 |
| 80°F | 159.0 | 136.2 |
| 81°F | 161.6 | 138.6 |
| 82°F | 164.2 | 141.1 |
| 83°F | 166.8 | 143.5 |
| 84°F | 169.5 | 146.0 |
| 85°F | 172.2 | 148.5 |
| 86°F | 174.9 | 151.1 |
| 87°F | 177.7 | 153.7 |
| 88°F | 180.4 | 156.3 |
| 89°F | 183.2 | 158.9 |
| 90°F | 186.1 | 161.6 |
| 91°F | 189.0 | 164.3 |
| 92°F | 191.9 | 167.0 |
| 93°F | 194.8 | 169.8 |
| 94°F | 197.8 | 172.6 |
| 95°F | 200.8 | 175.4 |
| 96°F | 203.8 | 178.3 |
| 97°F | 206.8 | 181.2 |
| 98°F | 209.9 | 184.1 |
| 99°F | 213.1 | 187.0 |
| 100°F | 216.2 | 190.0 |
| 101°F | 219.4 | 193.1 |
| 102°F | 222.6 | 196.1 |
| 103°F | 225.9 | 199.2 |
| 104°F | 229.1 | 202.3 |
| 105°F | 232.5 | 205.5 |
| 106°F | 235.8 | 208.7 |
| 107°F | 239.2 | 211.9 |
| 108°F | 242.6 | 215.2 |
| 109°F | 246.1 | 218.5 |
| 110°F | 249.5 | 221.9 |
| 111°F | 253.1 | 225.2 |
| 112°F | 256.6 | 228.6 |
| 113°F | 260.2 | 232.1 |
| 114°F | 263.8 | 235.6 |
| 115°F | 267.5 | 239.1 |
| 116°F | 271.2 | 242.7 |
| 117°F | 274.9 | 246.3 |
| 118°F | 278.7 | 249.9 |
| 119°F | 282.5 | 253.6 |
| 120°F | 286.3 | 257.3 |
| 121°F | 290.2 | 261.1 |
| 122°F | 294.1 | 264.9 |
| 123°F | 298.1 | 268.7 |
| 124°F | 302.0 | 272.6 |
| 125°F | 306.1 | 276.5 |
| 126°F | 310.1 | 280.5 |
| 127°F | 314.2 | 284.5 |
| 128°F | 318.4 | 288.5 |
| 129°F | 322.5 | 292.6 |
| 130°F | 326.8 | 296.8 |
| 131°F | 331.0 | 300.9 |
| 132°F | 335.3 | 305.2 |
| 133°F | 339.6 | 309.4 |
| 134°F | 344.0 | 313.7 |
| 135°F | 348.4 | 318.1 |
| 136°F | 352.9 | 322.5 |
| 137°F | 357.4 | 326.9 |
| 138°F | 361.9 | 331.4 |
| 139°F | 366.5 | 336.0 |
| 140°F | 371.1 | 340.6 |
| 141°F | 375.8 | 345.2 |
| 142°F | 380.5 | 349.9 |
| 143°F | 385.2 | 354.6 |
| 144°F | 390.0 | 359.4 |
| 145°F | 394.8 | 364.2 |
| 146°F | 399.7 | 369.1 |
| 147°F | 404.6 | 374.0 |
| 148°F | 409.5 | 379.0 |
| 149°F | 414.5 | 384.1 |
| 150°F | 419.6 | 389.1 |
| Temp (°C) | Bubble (kPa) | Dew (kPa) |
|---|---|---|
| −40°C | 15 | −17 |
| −39°C | 21 | −13 |
| −38°C | 27 | −9 |
| −37°C | 32 | −4 |
| −36°C | 39 | 1 |
| −35°C | 45 | 6 |
| −34°C | 51 | 11 |
| −33°C | 58 | 17 |
| −32°C | 65 | 22 |
| −31°C | 72 | 28 |
| −30°C | 80 | 34 |
| −29°C | 88 | 41 |
| −28°C | 96 | 47 |
| −27°C | 104 | 54 |
| −26°C | 112 | 61 |
| −25°C | 121 | 68 |
| −24°C | 130 | 76 |
| −23°C | 140 | 84 |
| −22°C | 149 | 92 |
| −21°C | 159 | 100 |
| −20°C | 169 | 109 |
| −19°C | 180 | 117 |
| −18°C | 191 | 127 |
| −17°C | 202 | 136 |
| −16°C | 213 | 146 |
| −15°C | 225 | 156 |
| −14°C | 237 | 166 |
| −13°C | 250 | 177 |
| −12°C | 263 | 188 |
| −11°C | 276 | 199 |
| −10°C | 289 | 211 |
| −9°C | 303 | 223 |
| −8°C | 318 | 235 |
| −7°C | 332 | 248 |
| −6°C | 347 | 261 |
| −5°C | 363 | 275 |
| −4°C | 379 | 289 |
| −3°C | 395 | 303 |
| −2°C | 412 | 318 |
| −1°C | 429 | 333 |
| 0°C H₂O freeze | 446 | 348 |
| 1°C | 464 | 364 |
| 2°C | 483 | 380 |
| 3°C | 502 | 397 |
| 4°C | 521 | 414 |
| 5°C | 541 | 432 |
| 6°C | 561 | 450 |
| 7°C | 582 | 469 |
| 8°C | 603 | 488 |
| 9°C | 625 | 507 |
| 10°C | 647 | 527 |
| 11°C | 669 | 548 |
| 12°C | 693 | 569 |
| 13°C | 716 | 590 |
| 14°C | 741 | 612 |
| 15°C | 765 | 635 |
| 16°C | 791 | 658 |
| 17°C | 816 | 681 |
| 18°C | 843 | 705 |
| 19°C | 870 | 730 |
| 20°C | 897 | 755 |
| 21°C | 926 | 781 |
| 22°C | 954 | 808 |
| 23°C | 984 | 835 |
| 24°C | 1,013 | 863 |
| 25°C | 1,044 | 891 |
| 26°C | 1,075 | 920 |
| 27°C | 1,107 | 949 |
| 28°C | 1,139 | 979 |
| 29°C | 1,172 | 1,010 |
| 30°C | 1,206 | 1,042 |
| 31°C | 1,240 | 1,074 |
| 32°C | 1,275 | 1,107 |
| 33°C | 1,311 | 1,140 |
| 34°C | 1,347 | 1,174 |
| 35°C | 1,384 | 1,209 |
| 36°C | 1,422 | 1,245 |
| 37°C | 1,460 | 1,281 |
| 38°C | 1,499 | 1,319 |
| 39°C | 1,539 | 1,356 |
| 40°C | 1,580 | 1,395 |
| 41°C | 1,621 | 1,435 |
| 42°C | 1,663 | 1,475 |
| 43°C | 1,706 | 1,516 |
| 44°C | 1,750 | 1,558 |
| 45°C | 1,794 | 1,600 |
| 46°C | 1,839 | 1,644 |
| 47°C | 1,885 | 1,688 |
| 48°C | 1,932 | 1,733 |
| 49°C | 1,979 | 1,779 |
| 50°C | 2,028 | 1,826 |
| 51°C | 2,077 | 1,874 |
| 52°C | 2,127 | 1,923 |
| 53°C | 2,178 | 1,973 |
| 54°C | 2,230 | 2,023 |
| 55°C | 2,282 | 2,075 |
| 56°C | 2,336 | 2,128 |
| 57°C | 2,390 | 2,181 |
| 58°C | 2,445 | 2,236 |
| 59°C | 2,502 | 2,291 |
| 60°C | 2,559 | 2,348 |
| 61°C | 2,617 | 2,406 |
| 62°C | 2,676 | 2,465 |
| 63°C | 2,735 | 2,525 |
| 64°C | 2,796 | 2,586 |
| 65°C | 2,858 | 2,648 |
| 66°C | 2,921 | 2,711 |
Full saturation values at 1° increments. Toggle between °F / PSIG and °C / kPa. Use Print / Save as PDF for laminated shop reference, or download the CSV / JSON below for use in other tools. R-427A PT chart data: CoolProp 7.2.0 (published Helmholtz equations of state / mixture models — see the source citations above).
Lower toxicity (Occupational Exposure Limit ≥ 400 ppm). No flame propagation in air at standard atmospheric pressure and 60°C. R-134a, R-22, R-410A, R-404A, R-744 (CO2) are A1.
- Flammability
- None (no flame propagation)
- Toxicity
- Lower (OEL ≥ 400 ppm)
Classification per ANSI/ASHRAE Standard 34-2022. See full reference.
Saturation pressure-temperature curve
Saturation values from CoolProp 7.2.0 mixture model: R-32/R-125/R-143a/R-134a, 15/25/10/50% by mass[3]. Operating pressure on a running system differs — see the operating-pressure references for in-use values.
At a glance
Chemistry
Lubricant compatibility
Marketed as 'simple retrofit' from R-22 — designed to work with any of MO/AB/POE oils.
Blend composition
- R-32 15.0%
- R-125 25.0%
- R-143a 10.0%
- R-134a 50.0%
Trade names
- Forane 427A — Arkema
Common applications
- R-22 retrofit (commercial AC, heat pumps, supermarket refrigeration)
- Compatible with mineral oil systems
Properties
- Boiling point (1 atm)bubble −45.4°F (−43.0°C), dew −33.2°F (−36.2°C)
- Critical pointNo single point — blend critical locus
- Molar mass90.44 g/mol
- Temperature glide10.5°F
- ODP0
- GWP (100-yr)2,138 US EPA value, 40 CFR 84.64(b) IPCC: AR4 2,138 · AR5 2,024 · AR6 2,397
- New-equipment status (US)Restricted in 44 new-equipment categories — US new-equipment rules (40 CFR 84.54).
What is R-427A?
R-427A is Arkema's four-component R-22 retrofit blend, developed in the 2000s alongside the other R-22 retrofit families (Chemours' ISCEON line — Freon MO99 (R-438A) and Freon MO29 (R-422D)). The composition includes 15% R-32 — the higher-volatility HFC component that contributes capacity — alongside the R-125, R-143a, and R-134a components that provide the operating envelope and non-flammability.
Unlike the hydrocarbon-aided R-22 retrofits (R-417A, R-422A, R-422D, R-438A), R-427A achieves mineral-oil compatibility through blend composition rather than a hydrocarbon additive.
Where R-427A is used
- R-22 retrofit (residential AC, heat pumps, light commercial)
- Medium-temperature commercial refrigeration (R-22 retrofit)
- Some compressor manufacturers' R-22 service literature names R-427A as a preferred retrofit
Regulatory & phase-down status
R-427A's GWP of 2,138 is above the 700-GWP limit for new residential and light-commercial AC and heat pumps (40 CFR 84.54(a)(1), (c)(1)). For new installations R-427A is not the choice; for R-22 retrofit work it remains commercially available.
Service notes
Compatible with mineral oil (MO), alkylbenzene (AB), and POE oils. R-427A has moderate temperature glide (~10-11°F at typical evaporator pressures); TXV operation may require attention after retrofit.
Temperature glide
R-427A is a zeotropic blend: at constant pressure it boils across a temperature range rather than at a single point. Use the dew curve for superheat, bubble curve for subcooling.
Operating cycle
Phase-down timeline
R-427A contains HFC-32, HFC-125, HFC-143a and HFC-134a, regulated substances under the AIM Act. Its GWP under 40 CFR 84.64 is 2,138, at or above the limit in 44 of the categories 40 CFR 84.54 restricts (listed under “All 84.54 categories restricting R-427A”).
- From January 1, 2025 — new self-contained residential & light-commercial AC and heat pump products: manufacture / import restricted (GWP ≥ 700).
- From January 1, 2025 — new residential & light-commercial AC and heat pump systems (except VRF): installation restricted (GWP ≥ 700), unless every specified component was manufactured or imported before January 1, 2025.
- From January 1, 2026 — new variable refrigerant flow (VRF) residential & light-commercial AC and heat pump systems: installation restricted (GWP ≥ 700); systems whose specified components were all manufactured or imported before January 1, 2026 may be installed until January 1, 2027, or until January 1, 2028 when a building permit issued before October 5, 2023 specifies the refrigerant.
- From January 1, 2027 — new supermarket systems: installation restricted (GWP ≥ 1,400).
- From January 1, 2028 — new self-contained residential & light-commercial AC and heat pump products: sale and distribution restricted (GWP ≥ 700).
- From January 1, 2032 — new supermarket systems: installation restricted at GWP ≥ 150 for systems with 200 lb or more of refrigerant (except the high-temperature side of a cascade system), and at GWP ≥ 300 for systems under 200 lb and for the high-temperature side of a cascade system.
HFC production & consumption allowances step down to 30% of baseline in 2029–2033, 20% of baseline in 2034–2035, and 15% of baseline in 2036 and later (42 U.S.C. 7675(e)(2)(C)).
US new-equipment rules (40 CFR 84.54)
R-427A contains HFC-32, HFC-125, HFC-143a and HFC-134a, regulated substances under the AIM Act. Under 40 CFR 84.64(b) its GWP is 2,138: each component's GWP times its mass fraction; components without a GWP under 84.64 are left out (84.64(c)). That value is compared against each 40 CFR 84.54 subsector limit below.
| Effective | Equipment subsector | Limit | Restriction | ¶ |
|---|---|---|---|---|
| January 1, 2025 | Self-contained residential & light-commercial AC and heat pump products | GWP ≥ 700 | Manufacture / import | (a)(1) |
| January 1, 2025 | Residential & light-commercial AC and heat pump systems (except VRF) | GWP ≥ 700 | Installation | (c)(1) |
| January 1, 2026 | Variable refrigerant flow (VRF) residential & light-commercial AC and heat pump systems | GWP ≥ 700 | Installation | (c)(2) |
| January 1, 2027 | Supermarket systems | GWP ≥ 1,400 | Installation | (c)(12)(i) |
| January 1, 2028 | Self-contained residential & light-commercial AC and heat pump products | GWP ≥ 700 | Sale / distribution | (b) |
| January 1, 2032 | Supermarket systems | GWP ≥ 150 (200 lb or greater, not the cascade high side); GWP ≥ 300 (less than 200 lb); GWP ≥ 300 (cascade high side) | Installation | (c)(12)(ii) |
All 84.54 categories restricting R-427A (44)
| Refrigeration, air conditioning & heat pumps (37) | |||
| January 1, 2025 | Self-contained residential & light-commercial AC and heat pump products | GWP ≥ 700 | (a)(1) |
| January 1, 2025 | Chillers for comfort cooling | GWP ≥ 700 | (a)(10)(i) |
| January 1, 2025 | Chillers for ice rinks | GWP ≥ 700 | (a)(10)(ii) |
| January 1, 2025 | Residential dehumidifiers | GWP ≥ 700 | (a)(2) |
| January 1, 2025 | Household refrigerators and freezers | GWP ≥ 150 | (a)(3) |
| January 1, 2025 | Retail food refrigeration — stand-alone units | GWP ≥ 150 | (a)(4) |
| January 1, 2025 | Vending machines | GWP ≥ 150 | (a)(5) |
| January 1, 2025 | Residential & light-commercial AC and heat pump systems (except VRF) | GWP ≥ 700 | (c)(1) |
| January 1, 2025 | Chillers for comfort cooling | GWP ≥ 700 | (c)(3) |
| January 1, 2025 | Ice rinks | GWP ≥ 700 | (c)(4) |
| January 1, 2026 | Chillers for industrial process refrigeration, fluid exiting the chiller warmer than −22°F (−30°C) | GWP ≥ 700 | (a)(10)(iii) |
| January 1, 2026 | Industrial process refrigeration products (non-chiller), charge 200 lb or greater, refrigerant entering the evaporator warmer than −22°F (−30°C) | GWP ≥ 150 | (a)(12)(i) |
| January 1, 2026 | Industrial process refrigeration products (non-chiller), charge less than 200 lb, refrigerant entering the evaporator warmer than −22°F (−30°C) | GWP ≥ 300 | (a)(12)(ii) |
| January 1, 2026 | Ice makers — batch type up to 1,000 lb of ice per 24 h and continuous type up to 1,200 lb per 24 h | GWP ≥ 150 | (a)(8)(i) |
| January 1, 2026 | Industrial process refrigeration systems (non-chiller), charge 200 lb or greater, evaporator inlet warmer than −22°F (−30°C), not the high-temperature side of a cascade | GWP ≥ 150 | (c)(10)(i) |
| January 1, 2026 | Industrial process refrigeration systems (non-chiller), charge less than 200 lb, evaporator inlet warmer than −22°F (−30°C) | GWP ≥ 300 | (c)(10)(ii) |
| January 1, 2026 | Industrial process refrigeration — high-temperature side of cascade systems, evaporator inlet warmer than −22°F (−30°C) | GWP ≥ 300 | (c)(10)(iii) |
| January 1, 2026 | Variable refrigerant flow (VRF) residential & light-commercial AC and heat pump systems | GWP ≥ 700 | (c)(2) |
| January 1, 2026 | Chillers for industrial process refrigeration, fluid exiting the chiller warmer than −22°F (−30°C) | GWP ≥ 700 | (c)(5)(i) |
| July 27, 2026 | Refrigerated transport — intermodal containers with a box temperature of −31°F (−35°C) or higher | GWP ≥ 700 | (a)(6) |
| July 27, 2026 | Retail food refrigeration — remote condensing units | GWP ≥ 1,400 | (c)(11)(i) |
| July 27, 2026 | Refrigerated transport — intermodal containers with a box temperature of −31°F (−35°C) or higher | GWP ≥ 700 | (c)(7) |
| July 27, 2026 | Cold storage warehouse systems | GWP ≥ 700 | (c)(9)(i) |
| January 1, 2027 | Self-contained products in data center, information technology equipment facility, and computer room cooling | GWP ≥ 700 | (a)(11) |
| January 1, 2027 | Refrigerated food processing and dispensing products outside the scope of UL 621, charge 500 g or less | GWP ≥ 150 | (a)(9)(i) |
| January 1, 2027 | Refrigerated food processing and dispensing products outside the scope of UL 621, charge greater than 500 g | listed refrigerant | (a)(9)(ii) |
| January 1, 2027 | Supermarket systems | GWP ≥ 1,400 | (c)(12)(i) |
| January 1, 2027 | Data center, information technology equipment facility, and computer room cooling systems | GWP ≥ 700 | (c)(13) |
| January 1, 2027 | Refrigerated food processing and dispensing equipment with a remote condenser | listed refrigerant | (c)(15) |
| January 1, 2028 | Chillers for industrial process refrigeration, fluid exiting the chiller from −58°F to −22°F (−50°C to −30°C) | GWP ≥ 700 | (a)(10)(iv) |
| January 1, 2028 | Industrial process refrigeration products (non-chiller), refrigerant entering the evaporator from −58°F to −22°F (−50°C to −30°C) | GWP ≥ 700 | (a)(12)(iii) |
| January 1, 2028 | Refrigerated food processing and dispensing products within the scope of UL 621 (ice cream makers) | listed refrigerant | (a)(9)(iii) |
| January 1, 2028 | Industrial process refrigeration systems (non-chiller), evaporator inlet from −58°F to −22°F (−50°C to −30°C) | GWP ≥ 700 | (c)(10)(iv) |
| January 1, 2028 | Chillers for industrial process refrigeration, fluid exiting the chiller from −58°F to −22°F (−50°C to −30°C) | GWP ≥ 700 | (c)(6)(i) |
| January 1, 2032 | Retail food refrigeration — remote condensing units | GWP ≥ 150 (200 lb or greater, not the cascade high side); GWP ≥ 300 (less than 200 lb); GWP ≥ 300 (cascade high side) | (c)(11)(ii) |
| January 1, 2032 | Supermarket systems | GWP ≥ 150 (200 lb or greater, not the cascade high side); GWP ≥ 300 (less than 200 lb); GWP ≥ 300 (cascade high side) | (c)(12)(ii) |
| January 1, 2032 | Cold storage warehouse systems | GWP ≥ 150 (200 lb or greater, not the cascade high side); GWP ≥ 300 (less than 200 lb); GWP ≥ 300 (cascade high side) | (c)(9)(ii) |
| Motor vehicle air conditioning (3) | |||
| October 24, 2024 | Motor vehicle air-conditioning in Model Year 2025 and later light-duty passenger cars and trucks (gross vehicle weight rating under 8,500 lb) | GWP ≥ 150 | (a)(13)(i) |
| Model Year 2028 | Motor vehicle air-conditioning in medium-duty passenger vehicles, heavy-duty pickup trucks and complete heavy-duty vans whose air-conditioning will not be modified by upfitters | GWP ≥ 150 | (a)(13)(ii) |
| January 1, 2028 | Motor vehicle air-conditioning in certain nonroad vehicles (agricultural tractors over 40 horsepower; self-propelled agricultural machinery; compact equipment; construction, forestry and mining equipment; and commercial utility vehicles) | GWP ≥ 150 | (a)(13)(iii) |
| Foam blowing agents (2) | |||
| January 1, 2025 | Foam products: rigid polyurethane appliance foam, commercial refrigeration foam, laminated boardstock, marine flotation foam, sandwich panels, slabstock; flexible polyurethane; integral skin polyurethane; polystyrene (extruded boardstock, billet, extruded sheet); phenolic insulation board and bunstock; polyisocyanurate laminated boardstock; polyolefin; rigid polyurethane spray foam | GWP ≥ 150 | (a)(14) |
| January 1, 2026 | Foam products in the (a)(14) formulations for use in space and military applications | GWP ≥ 150 | (a)(15) |
| Aerosol propellants / solvents (2) | |||
| January 1, 2025 | Aerosol products | GWP ≥ 150 | (a)(16)(i) |
| January 1, 2028 | Aerosol products (all, except defense sprays as defined in 84.3) | GWP ≥ 150 | (a)(16)(ii) |
Servicing. 40 CFR 84.54 restricts new manufacture/import, later sale/distribution, and installation. "Installation" is defined in 84.54(e); repairing or servicing existing R-427A equipment is not an installation unless it meets 84.54(e), so existing systems can keep being serviced. From January 1, 2029, servicing or repairing R-427A equipment in supermarket systems, refrigerated transport or automatic commercial ice makers must be done with reclaimed refrigerant[2].
EU (retail-food / cold-storage)
Under Regulation (EU) No 517/2014, since replaced by (EU) 2024/573, applying from March 11, 2024 (compared against the AR4 headline GWP), R-427A's GWP is at or above the limit in:
- Annex III row 11: Refrigerators and freezers for commercial use (hermetically sealed equipment) — GWP ≥ 150, from January 1, 2022.
- Annex III row 13: Multipack centralised refrigeration systems for commercial use with a rated capacity of 40 kW or more — GWP ≥ 150, from January 1, 2022 (the primary refrigerant circuit of a cascade system may use GWP below 1,500).
Source: 40 CFR 84.54, current through 91 FR 31329 (May 26, 2026). Installation defined at 40 CFR 84.54(e).
Global warming potential, in context
R-22 retrofit blends
Retrofit and replacement paths
R-427A replaces
Replacements for R-427A
R-427A vs R-22, R-32, R-454B: saturation pressure
| Temp | R-427A | R-22 | R-32 | R-454B |
|---|---|---|---|---|
| 0°F | 18.7 / 28.0 | 24.0(−14%) | 49.3(+76%) | 42.7 / 45.3(+62%) |
| 40°F | 61.2 / 76.8 | 68.6(−11%) | 121.0(+57%) | 107.0 / 112.0(+46%) |
| 70°F | 113.7 / 134.7 | 121.4(−10%) | 205.8(+53%) | 183.1 / 190.5(+41%) |
| 100°F | 190.0 / 216.2 | 195.9(−9%) | 325.7(+51%) | 290.9 / 300.8(+39%) |
Frequently asked
›How does R-427A compare to other R-22 retrofit blends?
R-427A has the lowest GWP (2,138) among the major mineral-oil-compatible R-22 retrofit blends. R-417A (2,346), R-421A (2,631), R-422D (2,729), R-438A (2,265) are similar in function but higher GWP. R-407C (1,774) is lower GWP than R-427A. R-427A's appeal is the combination of mineral-oil compatibility and the lowest GWP in that subset.
›What is the normal operating pressure of R-427A?
Operating pressure depends on evaporator load and ambient. The saturation pressures are in the PT table and the comparison table on this page.
›What lubricant does R-427A use?
Compatible with mineral oil (MO), alkylbenzene (AB), and POE. R-427A doesn't include a hydrocarbon component — the mineral-oil compatibility comes from the blend chemistry itself.
›Does R-427A have temperature glide?
Yes — about 10-11°F at typical evaporator pressures. Use the dew curve for superheat measurement. TXV systems may require retuning after retrofit; EXV systems handle the glide automatically.
›Is R-427A the same as Forane 427A?
Yes. Forane 427A is Arkema's commercial brand name; R-427A is the ASHRAE 34 designation. Forane is Arkema's refrigerant brand family — Forane 22, Forane 410A, Forane 134a, etc., spanning the HFC and HCFC product lines.
›What's the GWP of R-427A?
2138 (mass-weighted from R-32, R-125, R-143a, R-134a components). This is the lowest among the mineral-oil-compatible R-22 retrofit blends, though still above the 700-GWP limit for new residential and light-commercial AC and heat pumps (40 CFR 84.54(a)(1), (c)(1)).
Sources & citations
- [1]2017 Guideline for Assignment of Refrigerant Container Colors (AHRI Guideline N-2017). AHRI. 2017. https://www.ahrinet.org/system/files/2023-06/AHRI_Guideline_N_2017.pdf (accessed October 2, 2026)
- [2]40 CFR 84.112 — Reclamation. eCFR (Office of the Federal Register). up to date as of 9/25/2026. https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-C/section-84.112 (accessed October 2, 2026). 89 FR 82859, Oct. 11, 2024
- [3]CoolProp 7.2.0. CoolProp (I. H. Bell, J. Wronski, S. Quoilin, V. Lemort). https://coolprop.org/ (accessed October 2, 2026). Bell, I. H.; Wronski, J.; Quoilin, S.; Lemort, V. Pure and Pseudo-pure Fluid Thermophysical Property Evaluation and the Open-Source Thermophysical Property Library CoolProp. Ind. Eng. Chem. Res. 53, 2498–2508 (2014). https://doi.org/10.1021/ie4033999